Plan Review Notes For Permit 07050502 |
Permit Number |
07050502 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-31 12:36:23 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | 1.)PLEASE REVISE THE INSTALLATION SCHEDULE TO BE | | CONSISTENT WITH THE PRODUCT APPROVAL.FOR SHUTTER | | MOUNTING, YOU HAVE "HV" AND "WO".THE PRODUCT APPROVAL | | REFERS TO CONNECTION TYPES AS A THROUGH L, SEE SHEETS | | 13 THROUGH 15.YOU HAVE CIRCLED CONNECTION TYPES A, D, | | G, AND L.CONNECTION TYPE D REQUIRES 4" SPACING. | | REVISE INSTALLATION SCHEDULE AND CONFIRM THAT ANCHORING | | IS COMPLIANT FOR CONNECTION TYPE AND SUBSTRATE. | | | | 2.)CONNECTION TYPE A, SHEET 13, IS FOR POURED | | CONCRETE ONLY.THIS JOB (ACCORDING TO THE INSTALLATION | | SCHEDULE WHICH YOU COMPLETED) IS CBS SUBSTRATE. |
|