Plan Review Notes
Plan Review Notes For Permit 07050407
Permit Number 07050407
Review Stop B
Sequence Number 3
Notes
Date Text
2007-09-24 14:32:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)IMPACT RATED PRODUCTS WERE SUBMITTED.PLEASE
 REMOVE REFERENCES TO HURRICANE SHUTTERS FROM THE PLAN
 AS THEY ARE IN CONFLICT WITH OTHER PAPERWORK PROVIDED.
  
  
 2.)FOR THE FLAT DECK ROOF, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING.SPECIFY ENHANCED FASTENING FOR
 ZONES 2 AND 3.
  
 3.)SHOW HOW THE PARAPET WALL WILL RESIST WIND LOADS
 OF FBC R CHAPTER 3.HOW WILL THE BOLTS KEEP THE WALL
 FROM BEING PUSHED OVER?NO OTHER STRAPPING,
 REINFORCEMENT, OR BRACING IS SHOWN.PROVIDE
 CALCULATIONS.
  
 3RD REVIEW; BRACING WAS ADDED ON ONE SIDE.THIS
 ADDRESSES WIND GOING ONE DIRECTION; PLEASE ADDRESS WIND
 LOADS FROM THE SOUTH.ALSO, IT APPEARS THAT THIS
 BRACING WAS ADDED, BUT NOT CLOUDED.ALL CHANGES ARE TO
 BE CLEARLY INDICATED ON THE PLAN.
  
 4.)ADDRESSED.
  
 NEW COMMENT:
  
 5.)SHOW DIMENSION FROM GRADE TO BOTTOM OF FOOTING,
 FBC R 403.1.4.
  
 A SET HAS BEEN RETAINED.