Plan Review Notes
Plan Review Notes For Permit 07050407
Permit Number 07050407
Review Stop B
Sequence Number 1
Notes
Date Text
2007-06-04 12:00:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A SITE PLAN SHOWING THE PROPOSED
 IMPROVEMENT, TO SCALE, WITH DISTANCE TO THE PROPERTY
 LINES AND THE DISTANCE BETWEEN THE PROPOSED GARAGE AND
 THE EXISTING HOUSE, FBC*106.IF THE DISTANCE TO THE
 PROPERTY LINE IS LESS THAN 6', SHOW THE LOCATION OF THE
 BUILDING ON THE ADJACENT PROPERTY FBC R302.2.
  
 2.)DECLARE WIND DESIGN CRITERIA, FBC R301 INCLUDING
 COMPONENT & CLADDING PRESSURES FOR THE ROOF.
  
 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD, FBC*106.3.3.
  
 4.)FRONT WALL SECTION, WALL SECTION, SPECIFIES
 SHEATHING NAILING AS 6"OC.THIS IS IN CONFLICT WITH
 THE SCHEDULE (PLYWOOD SHEATHING FASTENER SCHEDULE) AND
 WITH FBC R2304.9.1.
  
 5.)THE GARAGE DOOR HAS A DESIGN PRESSURE LIMITATION
 OF +46.6, REQUIREMENT PER PLAN IS +49.
  
 6.)IMPACT PROTECTION IS REQUIRED, FBC R301.2.1.2.IF
 YOU ARE USING REMOVABLE SHUTTERS FOR THE WINDOW,
 PROVIDE HURRICANE SHUTTER PRODUCT APPROVAL AND COMPLETE
 THE ATTACHED INSTALLATION SCHEDULE OR PROVIDE THE
 INFORMATION IN ANOTHER FORMAT.
  
 7.)FOR THE FLAT DECK ROOF, INDICATE WHICH APPROVED
 ASSEMBLY YOU ARE USING.SPECIFY ENHANCED FASTENING FOR
 ZONES 2 AND 3.
  