Plan Review Notes For Permit 07050402 |
Permit Number |
07050402 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-21 11:54:40 | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | 1} PROVIDE A RISER DIAGRAM SHOWING ELECTRICAL | | CONNECTION OF ALL SERVICE AND GENERATOR EQUIPMENT | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC. | | | | 3} 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY | | SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE | | TIME.PROVIDE A LOAD CALCULATION SHOWING COMPLIANCE | | WITH THIS ARTICLE. | | | | 4} THE PERSON TAKING RESPONSIBILITY FOR THE | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | RESUBMITTING. | | | | THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|