Plan Review Notes
Plan Review Notes For Permit 07050378
Permit Number 07050378
Review Stop B
Sequence Number 1
Notes
Date Text
2007-05-31 10:59:01****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* CITY
 OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.COMPLETE THE ATTACHED INSTALLATION SCHEDULE OR
 PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.THE GENERIC INSTALLATION SCHEDULE
 SUBMITTED DOES NOT PROVIDE ENOUGH INFORMATION TO SHOW
 CODE COMPLIANCE AND ASSIST IN INSPECTIONS.THE ANCHOR
 SPACING IS TO BE SPECIFIC TO EACH OPENING.IF YOU WISH
 TO USE "GENERIC" ANCHORING, DESIGN THE JOB TO WORST
 CASE, AND CIRCLE THE PROPOSED ANCHOR SPACING ON THE
 GENERIC CHART YOU HAVE CREATED.FOR THIS PARTICULAR
 JOB, FOR INSTANCE, YOU COULD CIRCLE THE WORST CASE SPAN
 FOR C2 AND CIRCLE THE SPAN FOR OPENINGS 12 AND 11 WHICH
 USE C3 AND C4.THEN, THE "GENERIC" ANCHOR SCHEDULE
 PROVIDED WOULD BE ACCEPTABLE.PLEASE CONTACT ME IF YOU
 NEED FURTHER ASSISTANCE.
  
 2.THE INSTALLATION SCHEDULE PROVIDED INCLUDES TWO
 DIFFERENT EXPOSURE CLASSIFICATIONS, B AND C.THE
 CONTRACTOR IS TO DETERMINE THE EXPOSURE CATEGORY AND
 SUBMIT AN INSTALLATION SCHEDULE IN COMPLIANCE.YOU CAN
 DETERMINE EXPOSURE CATEGORY BY VIEWING THE AERIALS ON
 THE PAPA WEBSITE (WWW.PBCGOV.COM/PAPA).
  
  
  
  
  