2007-06-04 13:52:21****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE OPENING 3.A 13' SPAN, 3" EDGE DISTANCE,
 77PSF REQUIRES 8" SPACING FOR C1, BUT YOUR INSTALLATION
 SCHEDULE SPECIFIES 9".IF YOU FEEL THAT I HAVE MADE
 THIS COMMENT IN ERROR, AS YOU FELT ON OTHER PERMIT
 APPLICATIONS, PLEASE CONTACT ME TO SCHEDULE AN
 APPOINTMENT AFTER REVIEWING THE HIGHLIGHTED PRODUCT
 APPROVAL.
  