Date |
Text |
2007-05-15 08:33:05 | ** UNSAT ** |
| |
| ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE |
| ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK. |
| PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006 |
| REVISIONS. |
| PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002 |
| NFPA-72. |
| |
| 2) NOTE: PLEASE INDICATE THE NEW CIRCUITS ON A PANEL |
| SCHEDULE TO BE PROVIDED SHOWING THE EXISTING |
| SERVICE/PANEL SIZE WITH NEW LOADS AND CIRCUITS BEING |
| ADDED. |
| PLEASE CLARIFY THE REQUIRED DEDICATED CIRCUITS FOR EACH |
| AS SHOWN ON PLANS ALONG WITH THEIR OVER CURRENT |
| PROTECTION DEVICES, CONDUCTOR SIZES |
| 310.16, 240.4.408.4. |
| FBC 106.3.5.4 |
| |
| 3) NOTE: PLEASE BE SURE THE BATH IS CIRCUITED PER |
| 210.52D, 210.11C3 WHICH REQUIRES 20AMP AND #12 AWG. |
| |
| 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| MULTI-LEVEL BUILDING. |
| PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN |
| NFPA-72 OR CALL TO GO OVER. |
| NFPA-72 11.5.1.1, 11.8.3 |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |