Plan Review Notes
Plan Review Notes For Permit 07050289
Permit Number 07050289
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-15 08:33:05** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE
 ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK.
 PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006
 REVISIONS.
 PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002
 NFPA-72.
  
 2) NOTE: PLEASE INDICATE THE NEW CIRCUITS ON A PANEL
 SCHEDULE TO BE PROVIDED SHOWING THE EXISTING
 SERVICE/PANEL SIZE WITH NEW LOADS AND CIRCUITS BEING
 ADDED.
 PLEASE CLARIFY THE REQUIRED DEDICATED CIRCUITS FOR EACH
 AS SHOWN ON PLANS ALONG WITH THEIR OVER CURRENT
 PROTECTION DEVICES, CONDUCTOR SIZES
 310.16, 240.4.408.4.
 FBC 106.3.5.4
  
 3) NOTE: PLEASE BE SURE THE BATH IS CIRCUITED PER
 210.52D, 210.11C3 WHICH REQUIRES 20AMP AND #12 AWG.
  
 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE. PLEASE SEE THE DEFINITIONS IN
 NFPA-72 OR CALL TO GO OVER.
 NFPA-72 11.5.1.1, 11.8.3
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved