2007-05-09 08:46:08 | *** DENIED *** |
| 1) ENERGY CALCULATIONS ARE NOT NEEDED AS THEY WERE |
| SUBMITTED WITH BUILDING PERMIT. |
| |
| 2) PLEASE SHOW ON ALL PAGES OF PLANS COMPANY NAME, |
| ADDRESS, AND TELEPHONE NUMBER AND COMPANY LICENSE |
| NUMBER. |
| |
| 3) PLEASE SHOW ON ALL PAGES OF PLANS JOB ADDRESS. |
| |
| 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND |
| SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER |
| FBC 104.2.1 . |
| |
| 5) NEED A/C EQUIPMENT SCHEDULE WITH ALL PERTINENT |
| INFORMATION ON MECHANICAL PLANS. |
| |
| 6) SEE YELLOW HIGH LIGHT ON FIRST FLOOR PLAN, SHOW |
| MISSING SECTIONS OF DUCT WORK, AND SIZE OF SQUARE DUCT |
| TRUNK LINE. |
| |
| 7) PLANS SHOW AIR HANDLER IN CLOSET BUT STATE AIR |
| HANDLER IS IN ATTIC, PLEASE 'SHOW' THE AIR HANDLER IN |
| THE ATTIC. |
| |
| 8) SHOW ON PLANS HOW THE RETURN AIR IS TO GET BACK TO |
| THE AIR HANDLER IN THE ATTIC |
| |
| 9) SEE YELLOW HIGH LIGHT ON SECOND FLOOR PLAN RETURN |
| AIR TRANSFER DUCT TO BEDROOM NEEDS TO BE SIZED. |
| |
| 10) 10" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE |
| NEEDS TO BE 16" SEE 2004 FBC/R M1602.4 (A) AND (C) |
| EXCEPT. |
| |
| *** 2004 FBC/R M1602.4.BALANCED RETURN AIR MAY BE |
| ACHIEVED BY. |
| (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE |
| RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS |
| SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT |
| ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR |
| HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO |
| ACHIEVE PROPER RETURN AIR BALANCE. |
| (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET |
| THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR |
| EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY |
| ROOMS, EXCEPT THAT ALL SUPPLY |
| AIR INTO THE MASTER SUITE SHALL BE INCLUDED. PER 2004 |
| FBC/R M1602.4 . |
| |
| 11)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY. PER 2004 FBC 106.1.1. |
| |