Plan Review Notes
Plan Review Notes For Permit 07050266
Permit Number 07050266
Review Stop M
Sequence Number 1
Notes
Date Text
2007-05-09 08:46:08*** DENIED ***
 1) ENERGY CALCULATIONS ARE NOT NEEDED AS THEY WERE
 SUBMITTED WITH BUILDING PERMIT.
  
 2) PLEASE SHOW ON ALL PAGES OF PLANS COMPANY NAME,
 ADDRESS, AND TELEPHONE NUMBER AND COMPANY LICENSE
 NUMBER.
  
 3) PLEASE SHOW ON ALL PAGES OF PLANS JOB ADDRESS.
  
 4) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 5) NEED A/C EQUIPMENT SCHEDULE WITH ALL PERTINENT
 INFORMATION ON MECHANICAL PLANS.
  
 6) SEE YELLOW HIGH LIGHT ON FIRST FLOOR PLAN, SHOW
 MISSING SECTIONS OF DUCT WORK, AND SIZE OF SQUARE DUCT
 TRUNK LINE.
  
 7) PLANS SHOW AIR HANDLER IN CLOSET BUT STATE AIR
 HANDLER IS IN ATTIC, PLEASE 'SHOW' THE AIR HANDLER IN
 THE ATTIC.
  
 8) SHOW ON PLANS HOW THE RETURN AIR IS TO GET BACK TO
 THE AIR HANDLER IN THE ATTIC
  
 9) SEE YELLOW HIGH LIGHT ON SECOND FLOOR PLAN RETURN
 AIR TRANSFER DUCT TO BEDROOM NEEDS TO BE SIZED.
  
 10) 10" RETURN AIR TRANSFER DUCT TO THE MASTER SUITE
 NEEDS TO BE 16" SEE 2004 FBC/R M1602.4 (A) AND (C)
 EXCEPT.
  
 *** 2004 FBC/R M1602.4.BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET
 THESE REQUIREMENTS FOR PROPER BALANCED RETURN AIR
 EXCLUDING BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY
 ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE INCLUDED. PER 2004
 FBC/R M1602.4 .
  
 11)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY. PER 2004 FBC 106.1.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  