Date |
Text |
2007-10-10 10:10:48 | ** DENIED 3RD REVIEW ** |
| |
| 1) NOTE: PLEASE SEE PANEL SCHEDULE CALLS FOR NEW A/C |
| CONDENSING UNIT AND AIR HANDLER, HOWEVER THE PLANS NOW |
| HAVE THESE CROSSED OFF WITH A PEN. |
| PLEASE KNOW THAT IN NO CASE MAY HAND DRAWN CHANGES BE |
| MADE TO PLANS CROSSING ITEMS OFF ETC. |
| PLEASE CORRELATE AND ADJUST A/C AS NEEDED. NO CU OR AHU |
| ARE SHOWN ON PLANS, ( NOW CROSSED OFF). THEY WERE OK, |
| WHEN THESE WERE NOT CROSSED OUT. |
| PLEASE SEE 440.11, 210.63 ETC FOR A/C. |
| PLEASE SEE FLORIDA STATUTES 481.221 AS THESE PLANS |
| WHICH ARE SIGNED, DATED AND SEAL MAY NOT BE CHANGED IN |
| PEN OR PENCIL. MUST BE REPRINTED, SIGNED, DATED AND |
| SEALED. |
| |
| 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE SPECIFIC TO |
| THE RECESSED LIGHTS PER 13-606.1.ABC.1.2.4. |
| ** THIS WOULD HAVE BEEN REDLINED IF NOT FOR COMMENT #1 |
| ABOVE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |