Plan Review Notes
Plan Review Notes For Permit 07050223
Permit Number 07050223
Review Stop E
Sequence Number 3
Notes
Date Text
2007-10-10 10:10:48** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE PANEL SCHEDULE CALLS FOR NEW A/C
 CONDENSING UNIT AND AIR HANDLER, HOWEVER THE PLANS NOW
 HAVE THESE CROSSED OFF WITH A PEN.
 PLEASE KNOW THAT IN NO CASE MAY HAND DRAWN CHANGES BE
 MADE TO PLANS CROSSING ITEMS OFF ETC.
 PLEASE CORRELATE AND ADJUST A/C AS NEEDED. NO CU OR AHU
 ARE SHOWN ON PLANS, ( NOW CROSSED OFF). THEY WERE OK,
 WHEN THESE WERE NOT CROSSED OUT.
 PLEASE SEE 440.11, 210.63 ETC FOR A/C.
 PLEASE SEE FLORIDA STATUTES 481.221 AS THESE PLANS
 WHICH ARE SIGNED, DATED AND SEAL MAY NOT BE CHANGED IN
 PEN OR PENCIL. MUST BE REPRINTED, SIGNED, DATED AND
 SEALED.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE SPECIFIC TO
 THE RECESSED LIGHTS PER 13-606.1.ABC.1.2.4.
 ** THIS WOULD HAVE BEEN REDLINED IF NOT FOR COMMENT #1
 ABOVE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved