2007-08-09 13:10:06 | |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| ** DENIED ** |
| |
| |
| 1) NOTE:PLEASE INDICATE THE CORRECT SERVICE SIZE. |
| PLEASE SEE THE SERVICE IS STILL IN QUESTION. PLEASE SEE |
| RISER INDICATES AN EXISTING 150AMP PANEL YET THE PANEL |
| IS SHOWN AS 100AMP WITH A LOAD EXCEEDING THE RATING OF |
| THE PANEL. |
| THIS INFORMATION IS SHOWN ON SHEET #2 |
| PLEASE SEE 2005 NEC , 240, 408, 230.70 ETC. FBC |
| 106.3.5.4. |
| |
| 2) NOTE:PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR |
| WATER HEATERS IS THAT OF 125%. |
| THIS WAS NOT ADDRESSED AND STILL SHOWS LOAD AT 100%. |
| |
| 3) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT |
| NO NEW CU? THIS IS THE SAME NOTE AS PREVIOUS REVIEW. |
| SHEET 2 DOES NOT SHOW ANY CU AND REQUIRED DISCONNECT. |
| PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS |
| ETC. |
| PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11. |
| |
| 4) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES |
| NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD |
| CALCULATIONS. PLEASE SEE FOR EXAMPLE, THE SMALL |
| APPLIANCE CIRCUITS WHICH ARE REQUIRED TO MEET 210.11C1, |
| 210.52B1, 220.53. |
| PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING |
| DWELLING. |
| |
| 5) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| HEATER. 422.31, 422.360 |
| THIS IS THE SAME NOTE. PLANS CONTAINS A NOTE WHICH |
| STATES TO BE HARD WIRED, YET THE PLANS STILL DO NOT |
| INDICATE THE REQUIRED DISCONNECT. |
| |
| 6) NOTE: SAME NOTE, NO INFORMATION OR RESPONSE. |
| PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI PROTECTION?, |
| CIRCUIT ON PANEL ? LOAD? |
| FBC 106.1.2, 106.3.5.4 |
| |
| 7) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A |
| SYMBOL LEGEND AND NOW ONE IS PROVIDED, YET THE SYMBOL |
| LEGEND DOES NOT CORRELATE WITH ALL ELECTRICAL SYMBOLS |
| ON PLANS. PLEASE SEE FOR EXAMPLE THE SYMBOL BEING SHOWN |
| FOR THE AHU. |
| PLEASE SEE NOT DISCONNECT IS SHOWN FOR THE AHU AS |
| REQUIRED PER 440.11 |
| PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES ON PLANS |
| AND COORDINATE. |
| FBC 106.1.2 |
| |
| 8) NOTE:THIS IS THE SAME NOTE AS PREVIOUS REVIEWED |
| PLANS. |
| PLEASE SEE FBC 2004 W/2006 REVISIONS FOR RECESSED |
| LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER |
| 13-606.1.ABC.1.2.4. |
| |
| 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B)WITH |
| RESPECT TO REPEAT CODE COMPLIANT COMMENTS AS SOME ITEMS |
| WERE REPEATED FROM THE PREVIOUS REVIEW. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |