Plan Review Notes
Plan Review Notes For Permit 07050223
Permit Number 07050223
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-09 13:10:06 
  
  
  
  
  
  
  
  
  
  
  
  
  
 ** DENIED **
  
  
 1) NOTE:PLEASE INDICATE THE CORRECT SERVICE SIZE.
 PLEASE SEE THE SERVICE IS STILL IN QUESTION. PLEASE SEE
 RISER INDICATES AN EXISTING 150AMP PANEL YET THE PANEL
 IS SHOWN AS 100AMP WITH A LOAD EXCEEDING THE RATING OF
 THE PANEL.
 THIS INFORMATION IS SHOWN ON SHEET #2
 PLEASE SEE 2005 NEC , 240, 408, 230.70 ETC. FBC
 106.3.5.4.
  
 2) NOTE:PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR
 WATER HEATERS IS THAT OF 125%.
 THIS WAS NOT ADDRESSED AND STILL SHOWS LOAD AT 100%.
  
 3) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT
 NO NEW CU? THIS IS THE SAME NOTE AS PREVIOUS REVIEW.
 SHEET 2 DOES NOT SHOW ANY CU AND REQUIRED DISCONNECT.
 PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS
 ETC.
 PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11.
  
 4) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES
 NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD
 CALCULATIONS. PLEASE SEE FOR EXAMPLE, THE SMALL
 APPLIANCE CIRCUITS WHICH ARE REQUIRED TO MEET 210.11C1,
 210.52B1, 220.53.
 PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING
 DWELLING.
  
 5) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER. 422.31, 422.360
 THIS IS THE SAME NOTE. PLANS CONTAINS A NOTE WHICH
 STATES TO BE HARD WIRED, YET THE PLANS STILL DO NOT
 INDICATE THE REQUIRED DISCONNECT.
  
 6) NOTE: SAME NOTE, NO INFORMATION OR RESPONSE.
 PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI PROTECTION?,
 CIRCUIT ON PANEL ? LOAD?
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED A
 SYMBOL LEGEND AND NOW ONE IS PROVIDED, YET THE SYMBOL
 LEGEND DOES NOT CORRELATE WITH ALL ELECTRICAL SYMBOLS
 ON PLANS. PLEASE SEE FOR EXAMPLE THE SYMBOL BEING SHOWN
 FOR THE AHU.
 PLEASE SEE NOT DISCONNECT IS SHOWN FOR THE AHU AS
 REQUIRED PER 440.11
 PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES ON PLANS
 AND COORDINATE.
 FBC 106.1.2
  
 8) NOTE:THIS IS THE SAME NOTE AS PREVIOUS REVIEWED
 PLANS.
 PLEASE SEE FBC 2004 W/2006 REVISIONS FOR RECESSED
 LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER
 13-606.1.ABC.1.2.4.
  
 9) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B)WITH
 RESPECT TO REPEAT CODE COMPLIANT COMMENTS AS SOME ITEMS
 WERE REPEATED FROM THE PREVIOUS REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]