Plan Review Notes
Plan Review Notes For Permit 07050223
Permit Number 07050223
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-14 16:36:31** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE
 ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK.
 PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006
 REVISIONS.
 PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002
 NFPA-72.
  
 2) NOTE: PLEASE INDICATE THE CORRECT SERVICE SIZE. FBC
 106.3.5.4.
  
 3) NOTE: PLEASE SEE THE MISSING GFI PER 210.52D,
 210.8A
  
 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING
 IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS
 TO SHOW MEETING THE CURRENT CODE FOR SMOKE
 DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE
 EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES
 INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A
 MULTI-LEVEL BUILDING.
 PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON
 THE TYPE OF DEVICE.
 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SUBMIT A COMPLETED CODE COMPLIANT PANEL
 SCHEDULE PER 408.4, 310.16, 240.4.
 PLEASE REVISE CIRCUITS AND CIRCUIT NUMBERS ON PANEL
 SCHEDULE TO COORDINATE WITH ALL SPECIFIC ROOMS,
 CIRCUITS AND AREAS..
 FBC 106.3.5.4, 106.1.2
  
 6) NOTE: PLEASE VERIFY THE EXISTING AHU AS THE HEAT
 STRIP IS SHOWN AS 10KW, YET THE OVER CURRENT PROTECTION
 IS SHOWN AT 50AMPS WHICH IS TOO LOW. PLEASE SEE 424.3B
 FOR MINIMUM OF 125%
 220, 408.4, 240.4
 FBC 106.1.2, 106.3.5.4
  
 7) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR
 WATER HEATERS IS THAT OF 125%.
  
 8) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT
 NO NEW CU?
 PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS
 ETC.
 PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11.
  
 9) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE
 CONNECTION TO NEW FOOTER STEEL PER 250.50. PLEASE ALSO
 CLARIFY EXISTING OR NEW CONNECTION TO COLD WATER.
  
 10) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES
 NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD
 CALCULATIONS.
 PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING
 DWELLING.
  
 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER
 HEATER. 422.31, 422.360
  
 12) NOTE: PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI
 PROTECTION?, CIRCUIT ON PANEL ? LOAD?
 FBC 106.1.2, 106.3.5.4
  
 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON
 TITLE BLOCK FOR ARCHITECT. PLEASE INCLUDE PHONE # FOR
 CONTACTING.
 FAC 61G1-16.004.
  
 14) NOTE: PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES
 ON PLANS AND COORDINATE.
  
 15) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS FOR
 RECESSED LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER
 13-606.1.ABC.1.2.4.
  
 16) NOTE: PLEASE KNOW AS SOME INFORMATION HAS NOT YET
 BEEN SUBMITTED, SOME INFORMATION CAN NOT BE REVIEWED AT
 THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]