2007-05-14 16:36:31 | ** UNSAT ** |
| |
| ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| 1) NOTE:PLEASE SEE THAT PLANS ARE REQUIRED TO STATE |
| ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK. |
| PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006 |
| REVISIONS. |
| PLEASE ALSO INCLUDE THE 2005 NFPA-70 (NEC) AND THE 2002 |
| NFPA-72. |
| |
| 2) NOTE: PLEASE INDICATE THE CORRECT SERVICE SIZE. FBC |
| 106.3.5.4. |
| |
| 3) NOTE: PLEASE SEE THE MISSING GFI PER 210.52D, |
| 210.8A |
| |
| 4) NOTE: PLEASE SEE FBC R313 AS THE EXISTING DWELLING |
| IS REQUIRED TO BE BROUGHT UP TO CODE OR THE EXISTING IS |
| TO SHOW MEETING THE CURRENT CODE FOR SMOKE |
| DETECTION/SOUNDING DEVICES. PLEASE SHOW A LAYOUT OF THE |
| EXISTING DWELLING WHICH WILL REQUIRE SMOKE DEVICES |
| INSIDE AND OUTSIDE ALL BEDROOMS AND ON EACH LEVEL IF A |
| MULTI-LEVEL BUILDING. |
| PLEASE SHOW THE SMOKE DEVICES AS SA OR SD DEPENDING ON |
| THE TYPE OF DEVICE. |
| NFPA-72 11.5.1.1, 11.8.3 |
| |
| 5) NOTE: PLEASE SUBMIT A COMPLETED CODE COMPLIANT PANEL |
| SCHEDULE PER 408.4, 310.16, 240.4. |
| PLEASE REVISE CIRCUITS AND CIRCUIT NUMBERS ON PANEL |
| SCHEDULE TO COORDINATE WITH ALL SPECIFIC ROOMS, |
| CIRCUITS AND AREAS.. |
| FBC 106.3.5.4, 106.1.2 |
| |
| 6) NOTE: PLEASE VERIFY THE EXISTING AHU AS THE HEAT |
| STRIP IS SHOWN AS 10KW, YET THE OVER CURRENT PROTECTION |
| IS SHOWN AT 50AMPS WHICH IS TOO LOW. PLEASE SEE 424.3B |
| FOR MINIMUM OF 125% |
| 220, 408.4, 240.4 |
| FBC 106.1.2, 106.3.5.4 |
| |
| 7) NOTE: PLEASE SEE 422.13 AS THE MINIMUM LOADS FOR |
| WATER HEATERS IS THAT OF 125%. |
| |
| 8) NOTE: PLEASE SEE THE PLANS INDICATE A NEW AHU, BUT |
| NO NEW CU? |
| PLEASE VERIFY WHAT IS NEW, WHAT IS EXISTING, LOCATIONS |
| ETC. |
| PLEASE SEE MISSING DISCONNECT FOR AHU. 440.11. |
| |
| 9) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE |
| CONNECTION TO NEW FOOTER STEEL PER 250.50. PLEASE ALSO |
| CLARIFY EXISTING OR NEW CONNECTION TO COLD WATER. |
| |
| 10) NOTE: PLEASE SEE ITEMS ON PANEL SCHEDULE WITH DOES |
| NOT INCLUDE ANY LOADS ON SCHEDULE OR IN LOAD |
| CALCULATIONS. |
| PLEASE SEE 220.87 WHEN ADDING LOADS TO EXISTING |
| DWELLING. |
| |
| 11) NOTE: PLEASE SEE MISSING DISCONNECT FOR WATER |
| HEATER. 422.31, 422.360 |
| |
| 12) NOTE: PLEASE CLARIFY SPA, IS THIS ELECTRIC? GFI |
| PROTECTION?, CIRCUIT ON PANEL ? LOAD? |
| FBC 106.1.2, 106.3.5.4 |
| |
| 13) NOTE: PLEASE SEE MISSING COMPLETED INFORMATION ON |
| TITLE BLOCK FOR ARCHITECT. PLEASE INCLUDE PHONE # FOR |
| CONTACTING. |
| FAC 61G1-16.004. |
| |
| 14) NOTE: PLEASE INCLUDE SYMBOL LEGEND FOR ALL DEVICES |
| ON PLANS AND COORDINATE. |
| |
| 15) NOTE: PLEASE SEE FBC 2004 W/2006 REVISIONS FOR |
| RECESSED LIGHTS AND INCLUDE INFORMATION AS REQUIRED PER |
| 13-606.1.ABC.1.2.4. |
| |
| 16) NOTE: PLEASE KNOW AS SOME INFORMATION HAS NOT YET |
| BEEN SUBMITTED, SOME INFORMATION CAN NOT BE REVIEWED AT |
| THIS TIME. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |