2007-05-04 16:03:14 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| |
| ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| |
| ____2.)CONTRACTOR IS TO PROVIDE THE FOLLOWING |
| INFORMATION ON THE APPLICATION, SEE ATTACHED POLICY; |
| MEAN ROOF HEIGHT, ROOF PITCH, ROOF DECK TYPE, AREA OF |
| EACH ROOF TYPE |
| |
| ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| |
| _XX_4.)FOR THE FLAT DECK, SELECT AN ASSEMBLY WHICH |
| MEETS OR EXCEEDS THE DESIGN PRESSURES FOR ZONE 1 OR |
| HIGHLIGHT WHERE IN THE NOA ENHANCED FASTENING FOR THE |
| FIELD IS PERMITTED.A SET HAS BEEN RETAINED. |
| |
| ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| FASTENING FOR CORNER AND PERIMETER ZONES. |
| |
| _XX_ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| METHOD OF ATTACHMENT YOU ARE USING. |
| |
| ____ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| CONSULTANT REQUIRED FOR ENHANCED |