Plan Review Notes For Permit 07050189 |
Permit Number |
07050189 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-07 15:39:57 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 2) NEED TO ADD TO PLANS, COMPANY NAME, ADDRESS, AND | | TELEPHONE NUMBER. COMPANY LICENSE NUMBER. | | | | 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | 4) PLEASE SHOW ON PLANS HOW RETURN AIR IS GETTING FROM | | THE BEDROOMS BACK TO THE AIR HANDLER, SEE 2004 FBC/R | | M1602.4. | | | | 5) PLEASE SHOW LOCATION OF THE CONDENSER UNIT ON THE | | PLANS. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|