Plan Review Notes
Plan Review Notes For Permit 07050189
Permit Number 07050189
Review Stop M
Sequence Number 1
Notes
Date Text
2007-05-07 15:39:57*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 2) NEED TO ADD TO PLANS, COMPANY NAME, ADDRESS, AND
 TELEPHONE NUMBER. COMPANY LICENSE NUMBER.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  
 4) PLEASE SHOW ON PLANS HOW RETURN AIR IS GETTING FROM
 THE BEDROOMS BACK TO THE AIR HANDLER, SEE 2004 FBC/R
 M1602.4.
  
 5) PLEASE SHOW LOCATION OF THE CONDENSER UNIT ON THE
 PLANS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.