2007-05-09 16:43:03** UNSAT **
  
  
 1) NOTE:PLEASE KNOW THAT THE PLANS WILL BE ROUTED
 THROUGH ADDRESSING REVIEW AS THE PLANS AND FLOOR IS
 BEING SPLIT UP INTO THREE NEW TENANTS. THE SUITE/UNIT
 NUMERICAL DESIGNATIONS WILL BE ASSIGNED BY THIS
 OFFICE.
  
 PLEASE SEE PLANS SHOW THE SAME SUITE #400 WITH A, B OR
 C, WHICH DOES COORDINATE TO OUR SYSTEM OF ADDRESSING
 ETC.
 PLEASE BE AWARE OF COMMENTS FROM THIS TRADE AS
 CORRECTIONS TO PLANS MAY BE NEEDED.
 FBC 106.1.2
  
 2) NOTE: PLEASE SHOW THE COMPLETED CIRCUITING FOR NEW
 CIRCUITS AND PANELS WHICH THEY ARE GOING TO BE FED
 FROM.
 PLEASE SUBMIT PANEL SCHEDULES FOR NEW CIRCUITS. PLEASE
 CLARIFY HOW THESE WILL BE NEW TENANTS; HOWEVER PLANS DO
 NOT SEEM TO SHOW ANY PROPOSED TENANT METERS ETC?
 408.4, 310.16, 240.4
 FBC106.3.5.4
  
 3) NOTE: PLEASE INDICATE MAXIMUM TIMES ON THE OCCUPANCY
 DEVICES PER 13-415.1.ABC.1.1.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  