Date |
Text |
2007-05-09 16:43:03 | ** UNSAT ** |
| |
| |
| 1) NOTE:PLEASE KNOW THAT THE PLANS WILL BE ROUTED |
| THROUGH ADDRESSING REVIEW AS THE PLANS AND FLOOR IS |
| BEING SPLIT UP INTO THREE NEW TENANTS. THE SUITE/UNIT |
| NUMERICAL DESIGNATIONS WILL BE ASSIGNED BY THIS |
| OFFICE. |
| |
| PLEASE SEE PLANS SHOW THE SAME SUITE #400 WITH A, B OR |
| C, WHICH DOES COORDINATE TO OUR SYSTEM OF ADDRESSING |
| ETC. |
| PLEASE BE AWARE OF COMMENTS FROM THIS TRADE AS |
| CORRECTIONS TO PLANS MAY BE NEEDED. |
| FBC 106.1.2 |
| |
| 2) NOTE: PLEASE SHOW THE COMPLETED CIRCUITING FOR NEW |
| CIRCUITS AND PANELS WHICH THEY ARE GOING TO BE FED |
| FROM. |
| PLEASE SUBMIT PANEL SCHEDULES FOR NEW CIRCUITS. PLEASE |
| CLARIFY HOW THESE WILL BE NEW TENANTS; HOWEVER PLANS DO |
| NOT SEEM TO SHOW ANY PROPOSED TENANT METERS ETC? |
| 408.4, 310.16, 240.4 |
| FBC106.3.5.4 |
| |
| 3) NOTE: PLEASE INDICATE MAXIMUM TIMES ON THE OCCUPANCY |
| DEVICES PER 13-415.1.ABC.1.1. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |