Notes
Date Text
2008-01-30 16:41:37PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION **
 *** DENIED ***
 1) PLEASE SUBMITCOOLING LOAD CALCULATIONS AS A NEW
 SYSTEM IS BEING INSTALLED, SEE 2004 FBC 13-607.1.ABC.1
 OR 13-407.1.ABC.1.
  
 2) PLEASE SHOW THE LOCATION OF THE NEW A/C CONDENSER
 UNIT ON PLAN 3.1, SEE 2004 FBC/R M1307.3.
  
 3) PLEASE SHOW AN A/C EQUIPMENT SCHEDULE ON PLAN 3.1
 WITH ALL PERTINENT INFORMATION, SEE 2004 WPB AMEND.
 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]