Plan Review Notes For Permit 07050164 |
Permit Number |
07050164 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-09-19 09:38:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) AS NOTED IN LAST REVIEW, ENERGY CALCULATIONS NEED TO | | BE ON FORM600C-04R NOT FORM 600-04, SEE 2004 FBC | | 13-600.3.C. | | | | 2) WHEN SUBMITTING THE 'CORRECT' ENERGY CALCULATIONS | | HAVE THEM SIGNED BY THE OWNER/AGENT ALSO, PER 2004 FBC | | 13-600.3.ABC.2. | | | | 3) ENERGY CALCULATIONS LINE 9A1 SHOW WALL INSULATION IS | | R-5. PLANS PAGE 4.1 DETAIL 2/4.1 SHOWS NO INSULATION ON | | THE WALLS, SEE FBC 13-103.2. PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|