2007-09-19 09:38:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW, ENERGY CALCULATIONS NEED TO
 BE ON FORM600C-04R NOT FORM 600-04, SEE 2004 FBC
 13-600.3.C.
  
 2) WHEN SUBMITTING THE 'CORRECT' ENERGY CALCULATIONS
 HAVE THEM SIGNED BY THE OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) ENERGY CALCULATIONS LINE 9A1 SHOW WALL INSULATION IS
 R-5. PLANS PAGE 4.1 DETAIL 2/4.1 SHOWS NO INSULATION ON
 THE WALLS, SEE FBC 13-103.2. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]