2007-09-26 18:57:51 | PROJECT: 213 MURRAY ROAD/ # 07050164 |
| |
| PROJECT DETAIL: ENCLOSE CARPORT, ADD COVERED BREEZEWAY |
| AND REMODEL KITCHEN. |
| |
| APPLICABLE CODE REVIEW: 2004 FLORIDA RESIDENTIAL/ |
| BUILDING CODE WITH 2006 REVISIONS AND THE 2004 FEBC. |
| |
| STATUS: APPROVED |
| |
| PLAN REVIEW COMMENTS: |
| |
| NOTE: ITEMS MARKED "X" HAVE COMPLIED. |
| |
| |
| |
| X1) REQUIRE SHOP DRAWINGS FOR TS COLUMNS AS INDICATED |
| ON SHEET 4.1. |
| |
| X2) PLEASE PROVIDE CLARIFICATION: SHEET 2.1 LOGGIA |
| FOUNDATION PLAN INDICATES 3" DIAMETER STEEL COLUMN; |
| DETAIL 3/4.1 REFLECTS 3.5 X 3.5" TS COLUMN. |
| |
| X3) SUBMIT PRODUCT APPROVALS FOR ALL FRAMING |
| CONNECTORS. |
| |
| X4) PROVIDE DETAIL FOR NEW CMU WALLTO EXISTING CMU |
| WALL CONNECTION. |
| |
| X5)SUBMIT EPOXY SPECIFICATIONS. |
| |
| X6) PROVIDE MECHANICAL ATTACHMENT DETAIL FOR IN-FILL |
| WALL FRAMING TO CMU WALL. SEE DETAIL 1/4.1. |
| |
| X7) SPECIFY GRADE AND SPECIES OF LUMBER USED FOR WALL |
| FRAMING, HEADERS AND BEAMS. |
| |
| X8) INDICATE LENGTH OF CARRIAGE BOLTS AND THE DIAMETER |
| OF WASHERS TO BE INSTALLED. SEE WALL LEGEND, SHEET |
| 2.1. |
| |
| X9) SHOW DETAILS OF 3X12 WOOD BEAM: MECHANICAL |
| ATTACHMENT PATTERN AND SPLICE LOCATIONS IF APPLICABLE. |
| |
| X10) PROVIDE DETAILS INDICATING THE ATTACHMENT OF THE |
| NEW LOGGIA ROOF TO THE EXISTING GARAGE ROOF FRAMING. |
| |
| X11) PLEASE SHOW SECTION MARK 2/4.1 ON SHEET 2.1 OR |
| 3.1. |
| |
| X12) PLAN INDICATES 4043 SINGLE HUNG WINDOW |
| INSTALLATION; THE SUBMITTED P/A'S ARE FOR CASEMENT |
| WINDOWS. PLEASE CLARIFY. |
| |
| X13) PROVIDE COLUMN WRAP DETAIL. |
| |
| X14)WOOD BUCKS SHALL CONFORM TO THE FOLLOWING |
| BUILDING CODE SECTION: |
| |
| 1714.5.4.2 MASONRY, CONCRETE OR OTHER STRUCTURAL |
| SUBSTRATE. |
| WHERE THE WOOD SHIM OR BUCK THICKNESS IS LESS THAN 1? |
| INCHES (38 MM), WINDOW AND DOOR ASSEMBLIES SHALL BE |
| ANCHORED THROUGH THE MAIN FRAME OR BY JAMB CLIP OR |
| SUBFRAME SYSTEM, IN ACCORDANCE WITH THE MANUFACTURER?S |
| PUBLISHED INSTALLATION INSTRUCTIONS. ANCHORS SHALL BE |
| SECURELY FASTENED DIRECTLY INTO THE MASONRY, CONCRETE |
| OR OTHER STRUCTURAL SUBSTRATE MATERIAL. UNLESS |
| OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE |
| MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE |
| LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME TO THE |
| ROUGH OPENING SUBSTRATE. |
| WHERE THE WOOD BUCK THICKNESS IS 1? INCHES (38 MM) OR |
| GREATER, THE BUCK SHALL BE SECURELY FASTENED TO |
| TRANSFER LOAD TO THE MASONRY, CONCRETE OR OTHER |
| STRUCTURAL SUBTRATE AND THE BUCK SHALL EXTEND BEYOND |
| THE INTERIOR FACE OF THE WINDOW OR DOOR FRAME.WINDOW |
| AND DOOR ASSEMBLIES SHALL BE ANCHORED THROUGH THE MAIN |
| FRAME OR BY JAMB CLIP OR SUBFRAME SYSTEM OR THROUGH THE |
| FLANGE TO THE SECURED WOOD BUCK IN ACCORDANCE WITH THE |
| MANUFACTURER?S PUBLISHED INSTALLATION INSTRUCTIONS. |
| UNLESS OTHERWISE TESTED, BUCKS SHALL EXTEND BEYOND THE |
| INTERIOR FACE OF THE WINDOW OR DOOR FRAME SUCH THAT |
| FULL SUPPORT OF THE FRAME IS PROVIDED. SHIMS SHALL BE |
| MADE FROM MATERIALS CAPABLE OF SUSTAINING APPLICABLE |
| LOADS, LOCATED AND APPLIED IN A THICKNESS CAPABLE OF |
| SUSTAINING APPLICABLE LOADS. ANCHORS SHALL BE PROVIDED |
| TO TRANSFER LOAD FROM THE WINDOW OR DOOR FRAME ASSEMBLY |
| TO THE SECURED WOOD BUCK. |
| |
| X15)607.2REDUCTION OF STRENGTH. |
| ALTERATIONS SHALL NOT REDUCE THE STRUCTURAL STRENGTH OR |
| STABILITY OF THE BUILDING, STRUCTURE, OR ANY INDIVIDUAL |
| MEMBER THEREOF. |
| EXCEPTION: SUCH REDUCTION SHALL BE ALLOWED AS LONG AS |
| THE STRENGTH AND THE STABILITY OF THE BUILDING ARE NOT |
| REDUCED TO BELOW THE FLORIDA BUILDING CODE, BUILDING |
| LEVELS. |
| |
| 607.3NEW STRUCTURAL MEMBERS. |
| NEW STRUCTURAL MEMBERS IN ALTERATIONS, INCLUDING |
| CONNECTIONS AND ANCHORAGE, SHALL COMPLY WITH THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| X16) PLEASE SHOW ALLEXTERIOR BUILDING ELEVATIONS: |
| |
| 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS. |
| THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL |
| EXTERIOR ELEVATIONS: |
| |
| RESIDENTIAL (ONE- AND TWO-FAMILY):STRUCTURAL |
| REQUIREMENTS SHALL INCLUDE: |
| WALL SECTION FROM FOUNDATION THROUGH ROOF, INCLUDING |
| ASSEMBLY AND MATERIALS CONNECTOR TABLES WIND |
| REQUIREMENTS STRUCTURAL CALCULATIONS (IF REQUIRED) . |
| RESIDENTIAL (ONE- AND TWO-FAMILY) |
| |
| |
| |
| |
| PLAN REVIEW: KEN CONRAD |
| PHONE: 561.805.6666 |
| FAX:561.805.6676 |