Plan Review Notes
Plan Review Notes For Permit 07050155
Permit Number 07050155
Review Stop G
Sequence Number 1
Notes
Date Text
2007-05-09 11:32:41DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. THERE ARE ALREADY APPROVED SIGNED AND SEALED GAS
 DRAWINGS BY PROFESSIONAL ENGINEER BRUCE M.
 CIARLARIELLO, STATE REGISTRATION #62977 ON MASTER
 PERMIT #05110655 SHEET P-602, ANY REVISED CHANGES TO
 SAID DRAWINGS MUST BE MADE BY SAID DESIGN PROFESSIONAL
 OF RECORD PER FLORIDA STATUTES, CHAPTER 471. THERE
 ALREADY IS A GAS PERMIT PRINTED (#07030553 TO HYPOLUXO
 PLUMBING INC. FOR THE NATURAL GAS)IF IT IS YOUR
 INTENT TO ATTAIN A GAS PERMIT FOR THE EXTERIOR LP TANK
 AND PIPING TO THE GENERATOR PLEASE REFERENCE THE SAID
 MASTER NUMBER ON THE RESUBMITTAL AND MAKE SURE THE
 PERMIT CLERK REFLECTS THESE CHANGES ON THE FRONT SCREEN
 ON THE RESUBMITTAL.
  
 NOTE: THERE ARE TWO GAS TYPES INDICATED ON SHEET P-602
 OF THE APPROVED MASTER #05110655 (LP AND NATURAL). IT
 IS SUGGESTED THAT YOU CHECK WITH THE CONTRACTOR (WEST
 CONSTRUCTION INC.) ON THE MASTER PERMIT #05110655 AND
 REVIEW THE APPROVED DRAWINGS TO CORRELATE THIS
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721