Plan Review Notes
Plan Review Notes For Permit 07050148
Permit Number 07050148
Review Stop P
Sequence Number 1
Notes
Date Text
2007-05-18 08:32:05DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 1:THE SUBMITTED SANITARY ISOMETRIC RISER
 DIAGRAM DOES NOT REFLECT THE FLOOR PLAN IS IS NOT CODE
 COMPLIANT. PLEASE REFERENCE THE RED LINE SANITARY
 ISOMETRIC RISER DIAGRAM THAT REFLECTS THE FLOOR PLAN
 AND IS CODE COMPLIANT.
 NOTE: 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. PLEASE REFERENCE ELECTRICAL PLAN REVIEW COMMENTS #1
 AND #5 AND COMPLY ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  