Date |
Text |
2007-05-14 10:12:49 | ** UNSAT ** |
| |
| ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| 1) NOTE:PLEASE SEE MISSING TITLE BLOCKS FOR THE |
| DESIGNER OF RECORD AS REQUIRED PER FAC 61G15-23.002. |
| PLEASE SEE THE PLANS APPEAR TO BE SIGNED WITH |
| *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE, |
| PLEASE PROVIDE A NOTARIZED LETTER FOR SIGNATURE |
| VERIFICATION. THE LETTER IS TO BE SIGNED, DATED, SEALED |
| AND CORRECTLY NOTARIZED. NOTARY TO PLACE INFORMATION AS |
| REQUIRED PER FS 117.05 |
| |
| 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR NEW LOADS |
| TO NEW OR EXISTING SERVICE. IF EXISTING, PLEASE |
| INDICATE THE SIZE OF THE EXISTING SERVICE WITH NEW |
| LOADS. |
| PLEASE SEE NEC 220.87. |
| |
| 3) NOTE: PLEASE SEE THE MISSING DEDICATED BATH CIRCUIT |
| PER 210.11C3, 210.52. |
| (MUST BE #12 AND 20AMP.) |
| |
| 4) NOTE: PLEASE SHOW THE SMOKE DEVICES AS SA OR SD. |
| PLEASE SEE NFPA-72 DEFINITIONS FOR TYPE OF DEVICES |
| WHICH ARE BEING INSTALLED. PLANS SHOW THESE AS SD WHICH |
| WOULD MEAN THESE DEVICES ARE SMOKE DETECTION DEVICES |
| ONLY AND WOULD ONLY SEND SIGNAL TO SOUNDING DEVICES OR |
| FIRE ALARM SYSTEM WHICH IS NOT ON PLANS. PLEASE KNOW IF |
| THESE ARE INDEED SA WHICH IS SMOKE ALARMS, THESE WOULD |
| DETECT AND SOUND THE ALARM. |
| PLEASE CLARIFY. |
| ** PLEASE ALSO SEE FBC R313 AS THE EXISTING DWELLING IS |
| REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SHOW A LAYOUT |
| OF THE EXISTING DWELLING WHICH WILL REQUIRE SMOKE |
| DEVICES INSIDE AND OUTSIDE ALL BEDROOMS. |
| NFPA-72 11.5.1.1, 11.8.3 |
| |
| 5) NOTE: PLEASE SEE THAT PLANS ARE REQUIRED TO STATE |
| ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK. |
| PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006 |
| REVISIONS. |
| PLEASE ALSO INCLUDE THE 2005 NEC AND THE 2002 NFPA-72. |
| |
| 6) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING ALL |
| EXISTING AND NEW CIRCUITS. CIRCUITS ARE REQUIRED TO |
| MINIMUM PER NEC AND TO BE SPECIFIC TO ROOMS AND AREAS |
| IN WHICH THEY FEED. |
| PLEASE SEE 408.4, 310.16, 240.4. |
| |
| 7) NOTE: PLEASE SEE MISSING EGRESS LIGHTING FIXTURES |
| FOR BOTH ROOMS PER 210.70 AND NFPA-101 7.8. |
| PLEASE SEE PLANS ONLY SHOW A FAN IN BOTH LOCATIONS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |