Plan Review Notes
Plan Review Notes For Permit 07050148
Permit Number 07050148
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-14 10:12:49** UNSAT **
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 1) NOTE:PLEASE SEE MISSING TITLE BLOCKS FOR THE
 DESIGNER OF RECORD AS REQUIRED PER FAC 61G15-23.002.
 PLEASE SEE THE PLANS APPEAR TO BE SIGNED WITH
 *INITIALS*, IF THIS IS INDEED THE LEGAL SIGNATURE,
 PLEASE PROVIDE A NOTARIZED LETTER FOR SIGNATURE
 VERIFICATION. THE LETTER IS TO BE SIGNED, DATED, SEALED
 AND CORRECTLY NOTARIZED. NOTARY TO PLACE INFORMATION AS
 REQUIRED PER FS 117.05
  
 2) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR NEW LOADS
 TO NEW OR EXISTING SERVICE. IF EXISTING, PLEASE
 INDICATE THE SIZE OF THE EXISTING SERVICE WITH NEW
 LOADS.
 PLEASE SEE NEC 220.87.
  
 3) NOTE: PLEASE SEE THE MISSING DEDICATED BATH CIRCUIT
 PER 210.11C3, 210.52.
 (MUST BE #12 AND 20AMP.)
  
 4) NOTE: PLEASE SHOW THE SMOKE DEVICES AS SA OR SD.
 PLEASE SEE NFPA-72 DEFINITIONS FOR TYPE OF DEVICES
 WHICH ARE BEING INSTALLED. PLANS SHOW THESE AS SD WHICH
 WOULD MEAN THESE DEVICES ARE SMOKE DETECTION DEVICES
 ONLY AND WOULD ONLY SEND SIGNAL TO SOUNDING DEVICES OR
 FIRE ALARM SYSTEM WHICH IS NOT ON PLANS. PLEASE KNOW IF
 THESE ARE INDEED SA WHICH IS SMOKE ALARMS, THESE WOULD
 DETECT AND SOUND THE ALARM.
 PLEASE CLARIFY.
 ** PLEASE ALSO SEE FBC R313 AS THE EXISTING DWELLING IS
 REQUIRED TO BE BROUGHT UP TO CODE. PLEASE SHOW A LAYOUT
 OF THE EXISTING DWELLING WHICH WILL REQUIRE SMOKE
 DEVICES INSIDE AND OUTSIDE ALL BEDROOMS.
 NFPA-72 11.5.1.1, 11.8.3
  
 5) NOTE: PLEASE SEE THAT PLANS ARE REQUIRED TO STATE
 ALL RELEVANT CODES WITH RESPECT TO SCOPE OF WORK.
 PLEASE SEE THIS PROJECT IS UNDER THE FBC 2004 W/2006
 REVISIONS.
 PLEASE ALSO INCLUDE THE 2005 NEC AND THE 2002 NFPA-72.
  
 6) NOTE: PLEASE PROVIDE A PANEL SCHEDULE SHOWING ALL
 EXISTING AND NEW CIRCUITS. CIRCUITS ARE REQUIRED TO
 MINIMUM PER NEC AND TO BE SPECIFIC TO ROOMS AND AREAS
 IN WHICH THEY FEED.
 PLEASE SEE 408.4, 310.16, 240.4.
  
 7) NOTE: PLEASE SEE MISSING EGRESS LIGHTING FIXTURES
 FOR BOTH ROOMS PER 210.70 AND NFPA-101 7.8.
 PLEASE SEE PLANS ONLY SHOW A FAN IN BOTH LOCATIONS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved