Plan Review Notes For Permit 07050114 |
Permit Number |
07050114 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-18 14:41:54 | *** DENIED *** | | 1) INFORMATION MISSING FROM TITLE BLOCK ENGINEERS | | PRINTED NAME (MICHEL TEELE) AND LICENSE NUMBER. SEE FAC | | 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET | | CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE | | NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND | | LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS | | AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE | | ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT. | | | | 2) PLEASE SUBMIT DETAILED MANUFACTURER'S | | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR | | GENERATOR (2 COPY'S). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|