Date |
Text |
2007-05-24 15:33:15 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. FAC-61G15-23.002 SEAL SIGNATURE AND DATE |
| SHALL BE AFFIXED: |
| EACH SHEET OF PLANS AND PRINTS WHICH |
| MUST BE SEALED UNDER PROVISIONS OF |
| CHAPTER 471 SHALL BE SEALED, SIGNED AND |
| DATED BY THE PROFESSIONAL ENGINEER IN |
| RESPONSIBLE CHARGE. ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME, ADDRESS, |
| AND LICENSE NUMBER ON EACH SHEET. IF |
| PRACTICING THROUGH A DULY AUTHORIZED |
| ENGINEERING BUSINESS, ENGINEERS SHALL |
| LEGIBLY INDICATE THEIR NAME LICENSE NUM- |
| BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF |
| AUTHORIZATION NUMBER OF |
| THE ENGNEERING BUSINESS ON EACH SHEET. |
| |
| 2. PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S |
| SPECIFICATIONS INDICATING RECOMMENDED SETBACKS TO |
| ADJACENT STRUCTURES AND GAS SPEC'S TO VERIFY BTU LOAD |
| OF PROPOSED GENERATOR. |
| |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| 4. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| |
| 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL). |
| |
| 6. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. PLEASE |
| REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING |
| SAID RESIDENCE HAS GAS. |
| |
| 7. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: AGAIN THIS INCLUDES THE EXISTING GAS SYSTEM BTU |
| LOAD. |
| |
| 8. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| UNDILUTED PROPANE SPECIFY 10 PSI, 2 PSI OR 12 INCH WC. |
| |
| 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER |
| PLEASE SUBMIT MANUFACTURER SPECIFICATIONS FOR THE |
| REGULATOR INDICATING THE MANUFACTURERS NAME, MODEL |
| NUMBER, MAXIMUM LOAD CAPACITY AND SHOW A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). |
| |
| 10. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| |
| 11. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |