Plan Review Notes
Plan Review Notes For Permit 07050114
Permit Number 07050114
Review Stop G
Sequence Number 1
Notes
Date Text
2007-05-24 15:33:15DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. FAC-61G15-23.002 SEAL SIGNATURE AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
  
 2. PLEASE SUBMIT TWO COPIES OF MANUFACTURER'S
 SPECIFICATIONS INDICATING RECOMMENDED SETBACKS TO
 ADJACENT STRUCTURES AND GAS SPEC'S TO VERIFY BTU LOAD
 OF PROPOSED GENERATOR.
  
 3. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 4. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 5. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL).
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: THIS INCLUDES THE EXISTING GAS SYSTEM. PLEASE
 REFERENCE THE ATTACHED PERMIT INFORMATION INDICATING
 SAID RESIDENCE HAS GAS.
  
 7. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 NOTE: AGAIN THIS INCLUDES THE EXISTING GAS SYSTEM BTU
 LOAD.
  
 8. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 UNDILUTED PROPANE SPECIFY 10 PSI, 2 PSI OR 12 INCH WC.
  
 9. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: IF GAS DELIVERY PRESSURE IS 2 PSI OR GREATER
 PLEASE SUBMIT MANUFACTURER SPECIFICATIONS FOR THE
 REGULATOR INDICATING THE MANUFACTURERS NAME, MODEL
 NUMBER, MAXIMUM LOAD CAPACITY AND SHOW A LISTING FROM A
 NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL).
  
 10. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 11. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 END OF COMMENTS:
  