Plan Review Notes
Plan Review Notes For Permit 07050114
Permit Number 07050114
Review Stop E
Sequence Number 1
Notes
Date Text
2007-05-21 10:10:34 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE GENERATOR. PLEASE NOTE THAT
 TWO COPIES OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW.
  
 2} INDICATE THE GROUNDING ELECTRODE SYSTEM ON THE
 RISER. NOTE THAT PER 250.66 A #2CU CONDUCTOR IS
 REQUIRED. ALSO INDICATE HOW THE SYSTEM WILL BE
 RECONNECTED TO THE EXISTING GEC SYSTEM, NOTING THE
 CONCRETE ENCASED ELECTRODE BEING UTILIZED PER
 250.52(A)(3).
  
 3} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL
 INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG
 WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA
 ADMINISTRATIVE CODE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]