Plan Review Notes For Permit 07050114 |
Permit Number |
07050114 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-21 10:10:34 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING | | RECOMMENDED SETBACKS AND | | ELECTRICAL SPEC'S FOR THE GENERATOR. PLEASE NOTE THAT | | TWO COPIES OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | REVIEW. | | | | 2} INDICATE THE GROUNDING ELECTRODE SYSTEM ON THE | | RISER. NOTE THAT PER 250.66 A #2CU CONDUCTOR IS | | REQUIRED. ALSO INDICATE HOW THE SYSTEM WILL BE | | RECONNECTED TO THE EXISTING GEC SYSTEM, NOTING THE | | CONCRETE ENCASED ELECTRODE BEING UTILIZED PER | | 250.52(A)(3). | | | | 3} THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK SHALL | | INDICATE THE CERTIFICATE OF AUTHORIZATIONNUMBER ALONG | | WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 FLORIDA | | ADMINISTRATIVE CODE. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|