Plan Review Notes For Permit 07050102 |
Permit Number |
07050102 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-11-05 13:43:55 | RESIDENTIAL ADDITION BUILDING REVIEW FOURTH CHECKLIST. | | REVIEW UNDER EXISTING BUILDING 2004 CODE, FLORIDA | | RESIDENTIAL CODE 2004 AND FBC 2004. | | | | 1- DESIGN PARAMETERS INFORMATION IS MISSING THE ATTIC | | LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA | | RESIDENTIAL CODE. THIS IS THE FOURTH TIME THAT THIS | | INFORMATION IS REQUESTED. ARCHITECTTO PAY $524.80 AS | | REQUIRED BYFLORIDA STATUTE 553.80(2)(B) FOR PLAN | | REVIEW FEE. SEE ATTACHED COPY. | | | | ***NOTE: ONE COPY OF PLANS WILL BE RETAINED IN THIS | | OFFICE TO BE SUBMITTED TO THE BOARD OF ARCHITECTS FOR | | REVIEW. | | | | 2- ARCHITECT SPECIFIED CONSTRUCTION TYPE III. | | CONSTRUCTION TYPE III REQUIRES A TWO HOUR WALL ASSEMBLY | | AS REQUIRED BY TABLE 601 FBC 2004, THEREFORE,NEED TO | | PROVIDE MANUFACTURER'S SPECIFICATIONS FOR 2 HOUR FIRE | | RATED CONCRETE BLOCK.ALSO, ARCHITECT TO SPECIFYIF | | CONSTRUCTION TYPEIS A OR B. SEE TABLE 601 FBC 2004. | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | SEC. 713.13 FLORIDA STATUTE. THIS MAY BE PROVIDED WHEN | | PICKING UP THE PERMIT. | | | | 4- ENERGY CALCULATIONS: ONE OF THE COPIES IS MISSING | | THE INFORMATION ON TABLE 6C-1 AND TABLE 6C-2. COMPLETE | | INFORMATION AS REQUIRED. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|