Plan Review Notes
Plan Review Notes For Permit 07050102
Permit Number 07050102
Review Stop B
Sequence Number 4
Notes
Date Text
2007-11-05 13:43:55RESIDENTIAL ADDITION BUILDING REVIEW FOURTH CHECKLIST.
 REVIEW UNDER EXISTING BUILDING 2004 CODE, FLORIDA
 RESIDENTIAL CODE 2004 AND FBC 2004.
  
 1- DESIGN PARAMETERS INFORMATION IS MISSING THE ATTIC
 LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE. THIS IS THE FOURTH TIME THAT THIS
 INFORMATION IS REQUESTED. ARCHITECTTO PAY $524.80 AS
 REQUIRED BYFLORIDA STATUTE 553.80(2)(B) FOR PLAN
 REVIEW FEE. SEE ATTACHED COPY.
  
 ***NOTE: ONE COPY OF PLANS WILL BE RETAINED IN THIS
 OFFICE TO BE SUBMITTED TO THE BOARD OF ARCHITECTS FOR
 REVIEW.
  
 2- ARCHITECT SPECIFIED CONSTRUCTION TYPE III.
 CONSTRUCTION TYPE III REQUIRES A TWO HOUR WALL ASSEMBLY
 AS REQUIRED BY TABLE 601 FBC 2004, THEREFORE,NEED TO
 PROVIDE MANUFACTURER'S SPECIFICATIONS FOR 2 HOUR FIRE
 RATED CONCRETE BLOCK.ALSO, ARCHITECT TO SPECIFYIF
 CONSTRUCTION TYPEIS A OR B. SEE TABLE 601 FBC 2004.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE. THIS MAY BE PROVIDED WHEN
 PICKING UP THE PERMIT.
  
 4- ENERGY CALCULATIONS: ONE OF THE COPIES IS MISSING
 THE INFORMATION ON TABLE 6C-1 AND TABLE 6C-2. COMPLETE
 INFORMATION AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712