2007-10-11 14:30:38RESIDENTIAL ADDITION BUILDING REVIEW THIRD CHECKLIST.
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE,
 EXISTING BUILDING CODE 2004AND 2004 FBC 2004 WITH
 2006 REVISIONS.
  
 1-PLANS NEED TO CLEARLY SPECIFY ALL DESIGN LOADS,
 WIND LOADS, LIVE LOADS AND DEAD LOADS,INCLUDING THE
 ATTICLIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE.INFORMATION SUBMITTED UNDER
 DESIGN PARAMETERS ON SHEET 1 OF 4 DOESN'T MAKE SENSE.
 ITSHOWS LIVE LOAD OF 30 AND DEAD LOAD OF 15. WHAT ARE
 THESE LOADS FOR?.FLOOR, ROOF?.IT'S NOT CLEAR.ON
 THE OTHER HAND AT BOTTOM OFDESIGN PARAMETERS
 INFORMATION IT STATES "TOTAL ROOF DEAD LOAD OF 45". HOW
 WAS THIS LOAD ACHIEVED?.PROVIDECALCULATIONS.
 SECTION 106.1.2 CITY AMENDMENTS TO FBC 2004.PROVIDE
 CLEAR AND COORDINATEDINFORMATION SHOWING DESIGN LOADS
 FOR ROOF TOP CHORD LIVE AND DEAD LOADS ANDROOF BOTTOM
 CHORD LIVE AND DEAD LOADS. THIS IS THE INFORMATION
 REQUIRED FOR THE DESIGN OF ROOF TRUSSES. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 ***NOTES:A) SEE ATTACHED COPY OF SEC. 553.80(2)(B)
 REGARDING DESIGN PROFESSIONAL DOCUMENTS AND MULTIPLE
 PLAN REVIEW FAILURES.
 B) ONE COPY OF PLANS WILL BE
 RETAINED IN THIS OFFICE FOR FUTURE SUBMITTAL TO THE
 BOARD OF ARCHITECTS FOR REVIEW.
  
 2- THIS IS AN ADDITION, NOT ALTERATION LEVEL 3.SEE
 CHAPTER 9 OF EXISTING BUILDING 2004 CODE AND SCOPE OF
 WORK SPECIFIED ON PLANS AND REVISE INFORMATION AS
 REQUIRED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 4- ARCHITECT PROVIDED PRODUCT APPROVAL WITH THE REVIEW
 STAMP, BUT FAILED TO MARK ACTION TAKEN.STAMP DOESN'T
 STATE IF PRODUCT APPROVALWAS DENIED OR APPROVED.
 PROVIDE INFORMATION AS REQUIRED. SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004.
  
 5- MISSING THE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-600 FBC 2004.
  
 6- MISSING PRODUCT APPROVAL FOR SIMPSON CONNECTORS
 SPECIFIED ON PLANS. REQUIRED BY DCA RULE 9B-72.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER