2007-10-11 14:30:38 | RESIDENTIAL ADDITION BUILDING REVIEW THIRD CHECKLIST. |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE, |
| EXISTING BUILDING CODE 2004AND 2004 FBC 2004 WITH |
| 2006 REVISIONS. |
| |
| 1-PLANS NEED TO CLEARLY SPECIFY ALL DESIGN LOADS, |
| WIND LOADS, LIVE LOADS AND DEAD LOADS,INCLUDING THE |
| ATTICLIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 |
| FLORIDA RESIDENTIAL CODE.INFORMATION SUBMITTED UNDER |
| DESIGN PARAMETERS ON SHEET 1 OF 4 DOESN'T MAKE SENSE. |
| ITSHOWS LIVE LOAD OF 30 AND DEAD LOAD OF 15. WHAT ARE |
| THESE LOADS FOR?.FLOOR, ROOF?.IT'S NOT CLEAR.ON |
| THE OTHER HAND AT BOTTOM OFDESIGN PARAMETERS |
| INFORMATION IT STATES "TOTAL ROOF DEAD LOAD OF 45". HOW |
| WAS THIS LOAD ACHIEVED?.PROVIDECALCULATIONS. |
| SECTION 106.1.2 CITY AMENDMENTS TO FBC 2004.PROVIDE |
| CLEAR AND COORDINATEDINFORMATION SHOWING DESIGN LOADS |
| FOR ROOF TOP CHORD LIVE AND DEAD LOADS ANDROOF BOTTOM |
| CHORD LIVE AND DEAD LOADS. THIS IS THE INFORMATION |
| REQUIRED FOR THE DESIGN OF ROOF TRUSSES. SEC. 106.1.2 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| ***NOTES:A) SEE ATTACHED COPY OF SEC. 553.80(2)(B) |
| REGARDING DESIGN PROFESSIONAL DOCUMENTS AND MULTIPLE |
| PLAN REVIEW FAILURES. |
| B) ONE COPY OF PLANS WILL BE |
| RETAINED IN THIS OFFICE FOR FUTURE SUBMITTAL TO THE |
| BOARD OF ARCHITECTS FOR REVIEW. |
| |
| 2- THIS IS AN ADDITION, NOT ALTERATION LEVEL 3.SEE |
| CHAPTER 9 OF EXISTING BUILDING 2004 CODE AND SCOPE OF |
| WORK SPECIFIED ON PLANS AND REVISE INFORMATION AS |
| REQUIRED. |
| |
| 3- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| 4- ARCHITECT PROVIDED PRODUCT APPROVAL WITH THE REVIEW |
| STAMP, BUT FAILED TO MARK ACTION TAKEN.STAMP DOESN'T |
| STATE IF PRODUCT APPROVALWAS DENIED OR APPROVED. |
| PROVIDE INFORMATION AS REQUIRED. SEC. 106.3.3 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 5- MISSING THE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| 13-600 FBC 2004. |
| |
| 6- MISSING PRODUCT APPROVAL FOR SIMPSON CONNECTORS |
| SPECIFIED ON PLANS. REQUIRED BY DCA RULE 9B-72. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561) 805-6712 |