Plan Review Notes For Permit 07050102 |
Permit Number |
07050102 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-08-14 07:38:26 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | THESE COMMENTS ARE UNANSWERED FROM THE PREVIOUS | | REVIEW. | | | | COMMENTS MARKED WITH* ARE ADDITIONAL | | | | 1} LOCATE THE NEW WATER HEATER AND DISCONNECTON THE | | PLAN SO THAT COMPLIANCE WITH 110.26 AND 240.24 CAN BE | | DETERMINED. | | | | 2} THE 2 #4 FEEDERS TO THE WATER HEATER DISCONNECTON | | THE RISER DO NOT CORRELATE WITH THE #8CONDUCTORS IN | | THE PANEL SCHEDULE, AND A #6 ON A NOTE ON THE PLAN. | | CORRELATE SAME.REMOVE ALL NOTES AND CALCULATIONS NOT | | PERTINENT FOR RECORD KEEPING FROM THE PLAN FOR | | CLARITY. | | | | 3} THE FEEDER FOR THE WATER HEATER MUST GROUNDED PER | | 250.110 SIZED PER 250.122. | | | | 4} OK | | | | 5} THE FACT THAT THE 60 AMP DISCONNECT IS SHOWN "DOUBLE | | LUGGED" FROM THE METER, REQUIRES THAT IT BE SERVICE | | RATED PER 225.36. AND * GROUPED PER 230.70(A)(1) | | | | 6} 225.34(A) GENERAL THE TWO TO SIX DISCONNECTS AS | | PERMITTED IN 225.33 SHALL BE GROUPED. EACH DISCONNECT | | SHALL BE MARKED TO INDICATE THE LOAD SERVED. ALSO SEE | | 230.72(A) | | | | 7} THE WATER HEATER IS LISTEDIN THE PANEL SCHEDULE ON | | A 40 AMP BREAKER, BUT INDICATED AS HAVING A SEPARATE | | DISCONNECT ON THE RISER, CORRELATE SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|