2007-08-16 13:42:37 | ADDITION BUILDING REVIEW SECOND CHECKLIST: |
| REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC |
| 2004. |
| |
| 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPTAS |
| REQUESTED ON PREVIOUS CHECKLIST: |
| |
| 2- PLANS NEED TO SPECIFY ALL DESIGN LOADS, INCLUDING |
| THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004 |
| FLORIDA RESIDENTIAL CODE AND AS REQUESTED ON PREVIOUS |
| CHECKLIST. |
| |
| 3- SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BY SEC. |
| 602.1 FBC 2004 AND SEC. 106.3.5.4 OF CITY AMENDMENTS TO |
| FBC 2004. THIS ITEM WAS ALSO REQUESTED ON PREVIOUS |
| CHECKLIST. |
| |
| 4- STORM SHUTTERS: |
| A) INSTALLATION SCHEDULE SUBMITTED: |
| (1) PROVIDE COMPLETE AND CORRECTINSTALLATION |
| SCHEDULE. |
| (2)REVISE PRODUCT APPROVAL NUMBERS ON TOP OF FORM. |
| SEE SUBMITTED PRODUCT APPROVAL FOR CORRECT NUMBERS.. |
| (3) REVISE DESIGN PRESSURES. SEE ARCHITECTURAL PLANS |
| FOR CALCULATED DESIGN PRESSURES. |
| (4) REVISE INFORMATION GIVEN ON SHUTTER MOUNTING |
| COLUMN (COLUMN 4). LOOK AT SHUTTERS DRAWINGS AND |
| SPECIFY TYPE OF MOUNTING. EG: WALL MOUNTED, BUILT OUT |
| MOUNT, ETC.SPECIFIC MOUNTING CONDITION IS REQUIRED |
| SINCE THERE ARE MANY DIFFERENT MOUNTING CONDITIONS AND |
| TO VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| (5) WHAT'S THE SHUTTER GLASS SEPARATION.SEE |
| SHUTTERS DRAWINGS FOR REQUIRED SEPARATION. |
| (6) SPECIFY ANCHOR SPACING. |
| |
| B) CIRCLE ON SHUTTERSDRAWINGS SPECIFIC MOUNTING |
| CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| C) PROVIDE LEGIBLE DRAWINGS. DRAWING SUBMITTED ARE |
| NOT LEGIBLE. |
| |
| 5- TRUSS PACKAGE: |
| A) COMPLETE PACKAGE NEEDS TO HAVE ALL THE ENGINEER'S |
| INFORMATION AND ALL DRAWINGS TO BE SIGNED AND SEALED AS |
| REQUIRED BY SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA |
| STATUTE. |
| NOTE: COPY OF SIGNATURE IS NOT ALLOWED. |
| |
| B) COMPLETE TRUSS PACKAGE NEED TO BE REVIEWED AND |
| APPROVED BY THE ARCHITECT OF RECORD. NOT SIGNED AND |
| SEALED BY HIM. |
| NOTE: ARCHITECT CAN'T SIGN AND SEAL THESE DRAWINGS |
| BECAUSE THEY WERE NOT DONE BY HIM. SEE CHAPTER 481 |
| FLORIDA STATUTES. |
| |
| 6- SHEET 1 OF 4: |
| A) THIS IS AN ADDITION, NOT ALTERATION TYPE 2.SEE |
| CHAPTER 9 OF EXISTING FBC 2004 AND REVISE AS REQUIRED. |
| |
| |
| B) TOTAL ROOF DEAD LOAD LINE SHOWS 30PSF, WHILE DEAD |
| LOAD LINE SHOWS 25PSF. REVISE AND COORDINATE AS |
| REQUIRED.ALSO SEEITEM#2ABOVE. |
| |
| 7- REVISE GABLE END WALL SECTION. |
| A) ROOF SHEATHING NAIL SPACING NEEDS TO BE REVISED |
| FOR ROOF ZONE 3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA |
| RESIDENTIAL CODE AND REVISE AS REQUIRED. |
| |
| B) USP CONNECTORSPECIFIED DOESN'T MATCH CONNECTOR |
| SPECIFIED ON ROOF FRAMING PLAN AND TRUSS ANCHOR |
| SCHEDULE. REVISE AS REQUIRED. |
| |
| 8- REVISE ROOF SHEATHING NAIL SPACING SPECIFIED ON |
| TYPICAL WALL SECTION.SEE SEC. R803.2.3.1 OF 2004 |
| FLORIDA RESIDENTIAL CODE FOR NAIL SPACING AT ROOF ZONE |
| #3 AND REVISE AS REQUIRED. |
| |
| 9- TYPICAL WALL SECTION TITLE CALLS FOR 1'-6" O.H. |
| WHILE TYP. WALL SECTION DRAWINGS SHOW 24" OVERHANG. |
| REVISE AS REQUIRED TO MATCH. |
| |
| 10- CLARIFY WHY ARCHITECT REVIEWED AND APPROVED PRECAST |
| LINTEL PRODUCT APPROVAL FOR 4", 6 AND 12" PRECAST |
| LINTELS IF THERE ARE NOT LINTELS THIS SIZE?. SEE |
| PLANS. |
| |
| 11- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| SEC. 713.13 FLORIDA STATUTE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |