2007-08-16 13:42:37ADDITION BUILDING REVIEW SECOND CHECKLIST:
 REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND FBC
 2004.
  
 1- PROVIDE COPY OF IMPACT FEES PAID RECEIPTAS
 REQUESTED ON PREVIOUS CHECKLIST:
  
 2- PLANS NEED TO SPECIFY ALL DESIGN LOADS, INCLUDING
 THE ATTIC LIVE LOAD AS REQUIRED BY TABLE R301.5 OF 2004
 FLORIDA RESIDENTIAL CODE AND AS REQUESTED ON PREVIOUS
 CHECKLIST.
  
 3- SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BY SEC.
 602.1 FBC 2004 AND SEC. 106.3.5.4 OF CITY AMENDMENTS TO
 FBC 2004. THIS ITEM WAS ALSO REQUESTED ON PREVIOUS
 CHECKLIST.
  
 4- STORM SHUTTERS:
 A) INSTALLATION SCHEDULE SUBMITTED:
 (1) PROVIDE COMPLETE AND CORRECTINSTALLATION
 SCHEDULE.
 (2)REVISE PRODUCT APPROVAL NUMBERS ON TOP OF FORM.
 SEE SUBMITTED PRODUCT APPROVAL FOR CORRECT NUMBERS..
 (3) REVISE DESIGN PRESSURES. SEE ARCHITECTURAL PLANS
 FOR CALCULATED DESIGN PRESSURES.
 (4) REVISE INFORMATION GIVEN ON SHUTTER MOUNTING
 COLUMN (COLUMN 4). LOOK AT SHUTTERS DRAWINGS AND
 SPECIFY TYPE OF MOUNTING. EG: WALL MOUNTED, BUILT OUT
 MOUNT, ETC.SPECIFIC MOUNTING CONDITION IS REQUIRED
 SINCE THERE ARE MANY DIFFERENT MOUNTING CONDITIONS AND
 TO VERIFY COMPLIANCE WITH PROPOSED INSTALLATION. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
 (5) WHAT'S THE SHUTTER GLASS SEPARATION.SEE
 SHUTTERS DRAWINGS FOR REQUIRED SEPARATION.
 (6) SPECIFY ANCHOR SPACING.
  
 B) CIRCLE ON SHUTTERSDRAWINGS SPECIFIC MOUNTING
 CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. SEC.
 106.1.2 CITY AMENDMENTS TO FBC 2004.
  
 C) PROVIDE LEGIBLE DRAWINGS. DRAWING SUBMITTED ARE
 NOT LEGIBLE.
  
 5- TRUSS PACKAGE:
 A) COMPLETE PACKAGE NEEDS TO HAVE ALL THE ENGINEER'S
 INFORMATION AND ALL DRAWINGS TO BE SIGNED AND SEALED AS
 REQUIRED BY SEC. 61G15-23.002 AND CHAPTER 471 FLORIDA
 STATUTE.
 NOTE: COPY OF SIGNATURE IS NOT ALLOWED.
  
 B) COMPLETE TRUSS PACKAGE NEED TO BE REVIEWED AND
 APPROVED BY THE ARCHITECT OF RECORD. NOT SIGNED AND
 SEALED BY HIM.
 NOTE: ARCHITECT CAN'T SIGN AND SEAL THESE DRAWINGS
 BECAUSE THEY WERE NOT DONE BY HIM. SEE CHAPTER 481
 FLORIDA STATUTES.
  
 6- SHEET 1 OF 4:
 A) THIS IS AN ADDITION, NOT ALTERATION TYPE 2.SEE
 CHAPTER 9 OF EXISTING FBC 2004 AND REVISE AS REQUIRED.
  
  
 B) TOTAL ROOF DEAD LOAD LINE SHOWS 30PSF, WHILE DEAD
 LOAD LINE SHOWS 25PSF. REVISE AND COORDINATE AS
 REQUIRED.ALSO SEEITEM#2ABOVE.
  
 7- REVISE GABLE END WALL SECTION.
 A) ROOF SHEATHING NAIL SPACING NEEDS TO BE REVISED
 FOR ROOF ZONE 3. SEE SEC. R803.2.3.1 OF 2004 FLORIDA
 RESIDENTIAL CODE AND REVISE AS REQUIRED.
  
 B) USP CONNECTORSPECIFIED DOESN'T MATCH CONNECTOR
 SPECIFIED ON ROOF FRAMING PLAN AND TRUSS ANCHOR
 SCHEDULE. REVISE AS REQUIRED.
  
 8- REVISE ROOF SHEATHING NAIL SPACING SPECIFIED ON
 TYPICAL WALL SECTION.SEE SEC. R803.2.3.1 OF 2004
 FLORIDA RESIDENTIAL CODE FOR NAIL SPACING AT ROOF ZONE
 #3 AND REVISE AS REQUIRED.
  
 9- TYPICAL WALL SECTION TITLE CALLS FOR 1'-6" O.H.
 WHILE TYP. WALL SECTION DRAWINGS SHOW 24" OVERHANG.
 REVISE AS REQUIRED TO MATCH.
  
 10- CLARIFY WHY ARCHITECT REVIEWED AND APPROVED PRECAST
 LINTEL PRODUCT APPROVAL FOR 4", 6 AND 12" PRECAST
 LINTELS IF THERE ARE NOT LINTELS THIS SIZE?. SEE
 PLANS.
  
 11- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712