Plan Review Notes For Permit 07050102 |
Permit Number |
07050102 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-07 11:57:55 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM600C-04R, | | SEE 2004 FBC 13-600.3.C (12-8-06 REVISION). | | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | 2) MECHANICAL PERMIT #07050104 HAS BEEN APPLIED FOR BUT | | NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE | | SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY | | OF WPB AMEND. 106.3.5.4 (10). | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|