| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} LOCATE THE NEW WATER HEATER AND DISCONNECTON THE |
| PLAN SO THAT COMPLIANCE WITH 110.26 AND 240.24 CAN BE |
| DETERMINED. |
| |
| 2} THE 2 #4 FEEDERS TO THE WATER HEATER DISCONNECTON |
| THE RISER DO NOT CORRELATE WITH THE #8CONDUCTORS IN |
| THE PANEL SCHEDULE, AND A #6 ON A NOTE ON THE PLAN. |
| CORRELATE SAME.REMOVE ALL NOTES AND CALCULATIONS NOT |
| PERTINENT FOR RECORD KEEPING FROM THE PLAN FOR |
| CLARITY. |
| |
| 3} THE FEEDER FOR THE WATER HEATER MUST GROUNDED PER |
| 250.110 SIZED PER 250.122. |
| |
| 4} THE CIRCUIT NUMBERS ON THE PANEL SCHEDULE ARE |
| INCORRECT AND ARE DUPLICATED. SEE 408.4 2005 NEC |
| REGARDING"SPECIFIC PURPOSE OR USE". |
| |
| 5} THE FACT THAT THE 60 AMP DISCONNECT IS SHOWN "DOUBLE |
| LUGGED" FROM THE METER, REQUIRES THAT IT BE SERVICE |
| RATED PER 225.36. |
| |
| 6} 225.34(A) GENERAL THE TWO TO SIX DISCONNECTS AS |
| PERMITTED IN 225.33 SHALL BE GROUPED. EACH DISCONNECT |
| SHALL BE MARKED TO INDICATE THE LOAD SERVED. ALSO SEE |
| 230.72(A) |
| |
| 7} THE WATER HEATER IS LISTEDIN THE PANEL SCHEDULE ON |
| A 40 AMP BREAKER, BUT INDICATED AS HAVING A SEPARATE |
| DISCONNECT ON THE RISER, CORRELATE SAME. |
| |
| 8} THE ADDITION TO THE BEDROOMS DO NOT COMPLY WITH |
| 210.52(A)(1) & (2) FOR RECEPTACLE SPACING. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |