Date |
Text |
2007-06-20 16:47:57 | BUILDING REVIEW CHECKLIST: |
| 1- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| COUNTY FOR IMPACT FEES (2300N. JOG RD (561)233-5115). |
| BRING BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF |
| ADDITIONAL FEES ARE DUE. |
| |
| 2- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| 108.3CITY AMENDMENTS TO FBC 2004. THEREFORE, OWES |
| $80.19 FOR UPDATED VALUATION AND RADON FEES. |
| |
| 3- PLANS NEED TO SPECIFY ALL DESIGN LOADS, INCLUDING |
| THE ATTIC LIVE LOADS AS REQUIRED BY TABLE R301.5 OF |
| 2004 FLORIDA RESIDENTIAL CODE. |
| |
| 4- SPECIFY TYPE OF CONSTRUCTION AS REQUIRED BY SEC. |
| 602.1 FBC 2004. |
| |
| 5- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| 9B-72 FOR: |
| A) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS. |
| |
| B) ROOF SHINGLES. NOA 04-0820.01 SUBMITTED WAS |
| SUPERSEDED ACCORDING TO DADE COUNTY PRODUCT APPROVAL |
| WEBSITE. SEE ATTACHED COPY.NEED TO PROVIDE CURRENT |
| NOA OR PRODUCT APPROVAL. |
| ***NOTE: IF PROVIDING FLORIDA PRODUCT APPROVAL FL 183 |
| MAKE SURE NOA SUBMITTED CORRESPONDS TO SAME NOA |
| SUBMITTED FOR FLORIDA PRODUCT APPROVAL.GO THE THE |
| FLORIDA WEBSITE WWW.FLORIDABUILDING.ORG AND DOWNLOAD |
| CORRESPONDING NOA THAT WAS SUBMITTED FOR APPROVAL. |
| |
| 6- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND |
| APPROVED IN WRITING BY ARCHITECT OF RECORD. |
| ***NOTE: ONE PRODUCT APPROVAL FOR SINGLE HUNG WINDOW IS |
| MISSING THE ARCHITECT'S APPROVAL ON ONE COPY.ONLY THE |
| APPROVAL STAMP WAS SUBMITTED WITHOUT THE ARCHITECT'S |
| SIGNATURE. AND, MAKE SURE PRODUCT APPROVALS LISTED |
| ABOVE ARE APPROVED ALSO. |
| |
| 7- STORM SHUTTERS: |
| A) PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| ATTACHED SAMPLE AND COMPLETE ALL THE INFORMATION. |
| |
| B) CIRCLE ON ENGINEERED DRAWINGS SPECIFIC MOUNTING |
| CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. SEC. |
| 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| |
| C) PROVIDE LEGIBLE DRAWINGS. |
| |
| 8- ENERGY CALCULATIONS: |
| A) PROVIDE REVISED FORM 600C-04 R. |
| |
| B) COMPLETE ALL INFORMATION ON TOP OF FORM. |
| |
| C) REVISE PREDOMINANT EAVE OVERHANG LENGTH. SEE |
| PLANS. |
| |
| D) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| |
| 9- TRUSS PACKAGE: |
| A) COMPLETE PACKAGE NEEDS TO HAVE ALL THE ENGINEER'S |
| INFORMATION AND NEEDSTO BE SIGNED AND SEALED AS |
| REQUIRED BYCHAPTER 471 FLORIDA STATUTE AND SEC. |
| 61G15-23.002 FLORIDA ADMINISTRATIVE CODE.BOTH |
| COPIES. |
| |
| B) COMPLETE TRUSS PACKAGE NEEDS TO BE APPROVED BY THE |
| ARCHITECT OF RECORD. |
| |
| C) PROVIDE COMPLETE AND CORRECT TRUSS PACKAGE |
| INFORMATION TO THE BUILDING INSPECTOR AT TIME OF |
| FRAMING INSPECTION. |
| |
| |
| 10- SHEET 1 OF 4:. |
| A)THIS IS NOT AN ALTERATION LEVEL 2. SEE SEC. 307 OF |
| EXISTING BUILDING CODE AND REVISE AS REQUIRED. |
| |
| B) TOTAL ROOF DEAD LOAD LINE IN DESIGN PARAMETERS |
| INFORMATION IS BLANK. REVISE AS REQUIRED. |
| |
| 11- SHEET 2 OF 4: THIS IS NOT A FLOOR PLAN ADDITION |
| REVISION TO PERMIT 06080496. THIS IS A COMPLETE |
| SEPARATE PERMIT. REVISE NOTES AS REQUIRED. |
| |
| 12- SHEET 3 OF 4: |
| A) FOUNDATION PLAN NOTE REGARDING 8"X12" POURED |
| COLUMN DOESN'T MATCH INFORMATION SHOWN ON WALL AND BEAM |
| ATTACHMENT DETAIL ON SHEET 4 OF 4. REVISE AS REQUIRED |
| TO MATCH. |
| |
| B) GABLE END DETAIL: |
| * WHERE IS THE ROOF SHEATHING AND WALL SHEATHING |
| SCHEDULE?. |
| ** USP STRAP SPECIFIED DOESN'T MATCH INFORMATION |
| GIVEN ON ROOF FRAMING PLAN. REVISE AS REQUIRED TO MATCH |
| AND SEE TRUSS CONNECTOR CATALOG FOR PROPER SIZE AND |
| NUMBER OF FASTENERS REQUIRED. SEC. 106.1.2 CITY |
| AMENDMENTS STO FBC 2004. |
| |
| 13- SHEET 4 OF 4: |
| A) INFORMATION ON FOOTING ATTACHMENT DETAIL IS NOT |
| LEGIBLE. SEE MINIMUM EMBEDEMENT. REVISE AS REQUIRED. |
| |
| B) TYPICAL WALL SECTION: |
| * INSTALLING SHINGLES OR CEMENT TILE.ROOF LOADING |
| IS DIFFERENT. REVISE AS REQUIRED. |
| |
| ** REVISE TYPE OF NAIL REQUIRED FOR ROOF SHEATHING. |
| SEE SEC. R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE |
| FOR MIN. TYPE OF NAIL REQUIRED. |
| |
| *** REVISE TRUSS CONNECTOR TO MATCH TRUSS ANCHOR |
| SCHEDULE. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |
| (561)805-6712 |
| |
| |