2007-09-04 08:20:38 | 2007-09-04 08:20:38 |
| |
| ** DENIED2ND REVIEW** |
| |
| ** PLEASE SEE THE COMMENT BELOW FROM THE PREVIOUS |
| REVIEW. |
| |
| 1) NOTE: PLEASE BE SURE WHEN TYPING RESPONSE LETTERS TO |
| ACCURATELY DEPICT THE NOTES FORM THE REVIEWER AS TYPED |
| OR NOTED. PLEASE SEE NOTE #8 FROM THE PREVIOUS REVIEW |
| WHICH HAS CODES AND SECTIONS MIS-QUOTED FORM THE |
| PREVIOUS REVIEW. |
| THIS COULD VERY WELL LEAD TO CONFUSION OR |
| MISUNDERSTANDING OF THE NOTES. |
| |
| 2) NOTE: PLEASE SEE NOTE #8 FROM THE PREVIOUS REVIEW. |
| THE RESPONSE FROM DESIGNER SPEAKS OFLOADS AS BEING |
| DETERMINED FROM THE NEC FOR LOAD CALCULATIONS WHEREAS |
| THE NOTE HAD TO DO THE FBC CHAPTER 13 FOR LIGHTING |
| LOADS. |
| THE*MINIMUM* LOADS FIGURED FOR LIGHTING IN THE |
| SERVICE CALCULATIONS FOR SIZING A SERVICE AND BRANCH |
| CIRCUITS AS REQUIRED IN THE NEC (220) IS COMPLETELY |
| DIFFERENT THAN THE MAXIMUM LOADS FOR LIGHTING |
| ALLOWANCES PER THE FLORIDA ENERGY CODE. |
| PLEASE SEE THE PREVIOUS REVIEW NOTE #8 WHICH SPOKE OF |
| THE LOADS TO BE FIGURED FOR TRACK LIGHTING PER |
| 13-415.2.ABC.1.2. THIS IS A MAXIMUM ALLOWANCE BASED ON |
| THE TRACK LIGHTING FIXTURES OR LENGTH OF TRACK BASED ON |
| A MINIMUM AS SET FORTH BY THE FBC DEPENDING ON THE TYPE |
| OF TRACK LIGHTING BEING INSTALLED. |
| PLEASE ALSO SEE THE MAXIMUM LIGHTING ALLOWANCES PER |
| 13-415.2 |
| PLEASE PROVIDE THE INFORMATION FOR THESE MAXIMUM |
| LIGHTING LEVELS. |
| |
| 3) NOTE: PLEASE SEE AS OF THE THREE NEW SETS SUBMITTED |
| ONLY TWO SETS ARE COMPLETED BEING SIGNED, AND SEALED. |
| PLEASE KNOW ONLY TWO ARE NEEDED HOWEVER IF THREE IS |
| BEING SUBMITTED AND WANTING TO BE STAMPED FOR |
| PERMITTING AND CONTRACTOR'S FIELD SETS THESE WOULD ALL |
| NEED TO BE SIGNED, DATED AND SEALED. |
| *PLEASE SEE THE A-SHEETS IN ONE SET. |
| |
| PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |