2007-05-17 10:50:57** UNSAT**
  
 ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA
 BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
  
 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN
 EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS
 SHOWN.
 PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER
 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006
 REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC.
 PLEASE ALSO SEE THE PLANS INDICATE * PALM BEACH COUNTY*
 LOCAL AMENDMENTS.
 SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD
 ALSO BE ON COVER SHEETS.
 WE ARE UNDER THE 2005 NFPA-70. (NEC).
 PLEASE ALSO LIST THE FOLLOWING.
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE VERIFY THE LOCATION OF PROJECT AS THE
 SITE/LOCATION PLAN INDICATES TWO LOCATIONS.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK IS TO INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY
 EQUIPMENT/MATERIALS ETC ARE OWNER SUPPLIED.
 FBC 108.3
  
 4) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE
 SUBMITTED IS NOT COMPLETE AND NEEDS TO CONTAIN
 SPECIFICS FOR CIRCUITING TO ROOMS AND AREAS IN WHICH
 THEY FEED.
 PLEASE ALSO INCLUDE EXISTING CIRCUITING AS THERE ARE
 REQUIRED ITEMS MISSING NOT ON PANEL SCHEDULE. *SEE NOTE
 FOR LOAD CALCULATIONS.
  
 5) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT. NEW
 ORE EXISTING?
 408.4, 220, ETC.
  
 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER
 210.62. NEW OR EXISTING?
 PLEASE ALSO SEE 220.43 FOR LOADS.
  
 7) NOTE: PLEASE COMPLETE AND COORDINATE LOAD
 CALCULATIONS. PLEASE SEE THE CODE SECTIONS REFLECTED
 ARE THAT FROM THE PREVIOUS CODE. PLEASE SEE THE
 RECEPTACLE LOAD MAY NOT BE USED AS 1VA PER FT, WHEN A
 KNOWN RECEPTACLE LOAD IS AVAILABLE. PLEASE SEE THAT THE
 PLANS MENTIONS ALL RECEPTACLES ARE EXISTING, HOWEVER
 NOT SHOWN, SO PLEASE CORRELATE.
 PLEASE SEE OTHER NOTES FOR RECEPTACLES.
 PLEASE SEE THAT LOADS SHOWN BELOW PANEL SCHEDULE DO NOT
 CORRELATE WITH THAT OF THE LOAD CALCULATIONS ON THE
 SAME SHEET.
 PLEASE SEE THE 2005 NEC.220.
  
 8) NOTE: PLEASE CLARIFY THE BUILDING. AT THIS TIME THIS
 SPACE APPEARS TO BE PART OF A LARGER BUILDING AND MAY
 NOT MEET THE DEFINITION OF BUILDING.
 PLEASE SEE FBC CHAPTER 1313-415.1.ABC.1.1, .1.2 AND
 .1.3 FOR POSSIBLE LIGHTING CONTROLS REQUIRED. PLEASE
 SEE 13-415.2 AS PERFORMANCE CALCULATIONS ARE REQUIRED
 FOR ANY SIZE BUILDING.
 PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOADS TO
 BE SHOWN. (HIGHER OF THE TWO AS SHOWN BASED ON FIXTURES
 OR LINEAR FT OF TRACK) FOR 120V SYSTEMS.
  
 ** PLEASE KNOW AS SOME ITEMS ARE NOT CLEAR AT THIS
 TIME, ALL COMMENTS FOR CODE COMPLIANCE AND REVIEW CAN
 NOT BE DONE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]