2007-05-17 10:50:57 | ** UNSAT** |
| |
| ** PLEASE SEE REFERENCES TO CHAPTER 1 OF THE FLORIDA |
| BUILDING CODE IS THE ADMINISTRATIVE SECTION AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| |
| 1) NOTE: PLEASE SEE PLANS MUST REFLECT CURRENT CODES IN |
| EFFECT AND ADOPTED BY THE STATE IN THE SCOPE OF WORK AS |
| SHOWN. |
| PLEASE KNOW HOWEVER AT THIS TIME AND AS OF DECEMBER |
| 8TH, 2006 THE STATE IS UNDER THE 2004 FBC W/2006 |
| REVISIONS. THESE ARE ONLY REVISIONS TO THE 2004 FBC. |
| PLEASE ALSO SEE THE PLANS INDICATE * PALM BEACH COUNTY* |
| LOCAL AMENDMENTS. |
| SOME OF THESE ARE STATED ON ELECTRICAL HOWEVER SHOULD |
| ALSO BE ON COVER SHEETS. |
| WE ARE UNDER THE 2005 NFPA-70. (NEC). |
| PLEASE ALSO LIST THE FOLLOWING. |
| 2003 NFPA-101 |
| 2002 NFPA-72 |
| |
| 2) NOTE: PLEASE VERIFY THE LOCATION OF PROJECT AS THE |
| SITE/LOCATION PLAN INDICATES TWO LOCATIONS. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF |
| WORK IS TO INCLUDE ALL LABOR AND MATERIALS EVEN IF ANY |
| EQUIPMENT/MATERIALS ETC ARE OWNER SUPPLIED. |
| FBC 108.3 |
| |
| 4) NOTE: PLEASE SEE 408.4 AS THE PANEL SCHEDULE |
| SUBMITTED IS NOT COMPLETE AND NEEDS TO CONTAIN |
| SPECIFICS FOR CIRCUITING TO ROOMS AND AREAS IN WHICH |
| THEY FEED. |
| PLEASE ALSO INCLUDE EXISTING CIRCUITING AS THERE ARE |
| REQUIRED ITEMS MISSING NOT ON PANEL SCHEDULE. *SEE NOTE |
| FOR LOAD CALCULATIONS. |
| |
| 5) NOTE: PLEASE SEE 600.5 FOR MISSING SIGN CIRCUIT. NEW |
| ORE EXISTING? |
| 408.4, 220, ETC. |
| |
| 6) NOTE: PLEASE SEE MISSING SHOW WINDOW RECEPTACLES PER |
| 210.62. NEW OR EXISTING? |
| PLEASE ALSO SEE 220.43 FOR LOADS. |
| |
| 7) NOTE: PLEASE COMPLETE AND COORDINATE LOAD |
| CALCULATIONS. PLEASE SEE THE CODE SECTIONS REFLECTED |
| ARE THAT FROM THE PREVIOUS CODE. PLEASE SEE THE |
| RECEPTACLE LOAD MAY NOT BE USED AS 1VA PER FT, WHEN A |
| KNOWN RECEPTACLE LOAD IS AVAILABLE. PLEASE SEE THAT THE |
| PLANS MENTIONS ALL RECEPTACLES ARE EXISTING, HOWEVER |
| NOT SHOWN, SO PLEASE CORRELATE. |
| PLEASE SEE OTHER NOTES FOR RECEPTACLES. |
| PLEASE SEE THAT LOADS SHOWN BELOW PANEL SCHEDULE DO NOT |
| CORRELATE WITH THAT OF THE LOAD CALCULATIONS ON THE |
| SAME SHEET. |
| PLEASE SEE THE 2005 NEC.220. |
| |
| 8) NOTE: PLEASE CLARIFY THE BUILDING. AT THIS TIME THIS |
| SPACE APPEARS TO BE PART OF A LARGER BUILDING AND MAY |
| NOT MEET THE DEFINITION OF BUILDING. |
| PLEASE SEE FBC CHAPTER 1313-415.1.ABC.1.1, .1.2 AND |
| .1.3 FOR POSSIBLE LIGHTING CONTROLS REQUIRED. PLEASE |
| SEE 13-415.2 AS PERFORMANCE CALCULATIONS ARE REQUIRED |
| FOR ANY SIZE BUILDING. |
| PLEASE SEE 13-415.2.ABC.1.2 FOR TRACK LIGHTING LOADS TO |
| BE SHOWN. (HIGHER OF THE TWO AS SHOWN BASED ON FIXTURES |
| OR LINEAR FT OF TRACK) FOR 120V SYSTEMS. |
| |
| ** PLEASE KNOW AS SOME ITEMS ARE NOT CLEAR AT THIS |
| TIME, ALL COMMENTS FOR CODE COMPLIANCE AND REVIEW CAN |
| NOT BE DONE AT THIS TIME. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |