2007-09-17 15:57:33REVIEW #: 2
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. OK
  
 3. THE TAG FOR THE FAN HAS BEEN CHANGED. HOWEVER, THE
 FAN IS STILL LISTED AS AN "EXHAUST FAN" ON PG H-0.1.
 PLEASE CORRECT.
  
 4. THE 1415 CFM REQUIRED FOR THIS SPACE IS 56.6% OF THE
 VOLUME OF OUTDOOR AIR SUPPLIED BY THE BASE BUILDING
 HVAC SYSTEM. HOW DOES THIS COMPARE TO THE PERCENTAGE OF
 OCCUPIABLE FLOOR AREA USED BY THIS TENANT? HOW MUCH IS
 LEFT AFTER REQUIREMENTS ARE MET FOR COMMON AREAS SUCH
 AS CORIDORS, ELEVATOR LOBBIES AND GANG BATHROOMS?
  
 5. THE INPUT DATA FOR THE EXTERIOR WALLS SHOULD NOT BE
 CHANGED TO A NEW, HIGHER VALUE, AS THE 4" INSULATION IS
 ONLY BEING INSTALLED ABOVE THE CEILING IN THE PLENUM
 AREAS AND NOT ON EXTERIOR WALLS FROM FLOOR TO CEILING.
 ALSO, DETAIL 9 ON A012.01 DOES NOT SHOW AN APPROVED AIR
 BARRIER (1/2 INCH GYPSUM WALL BOARD, TAPED AND SEALED
 OR UL 181 DUCT, TAPED AND SEALED) AS REQUIRED BY FBC
 13-410.1.ABC.3.6, 410.1.ABC.3.7, 410.1.ABC.3.3.7.1. SEE
 ALSO FBC,M 603.8, 603.9, 603.9.1.
  
  