Plan Review Notes
Plan Review Notes For Permit 07050059
Permit Number 07050059
Review Stop P
Sequence Number 1
Notes
Date Text
2007-06-09 17:53:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS SHALL INCLUDE THE FOLLOWING
 INFORMATION IN THE TITLE BLOCK AS REQUIRED BY FAC
 61G1-16.004(2)(5)(6) & FA 481.219, 481.2055. THE FIRM
 LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENTS, AND
 THE DATE THAT THE SIGNATURE AND SEAL ARE AFFIXED SHALL
 BE INDICATED BELOW THE SIGNATURE.
  
 2. ALL ARCHITECTURAL SHEETS. THE ADDRESS ON FILE WITH
 THE STATE DBPR WEBSITE DOES NOT REFLECT THE ADDRESS
 INDICATED IN THE TITLE BLOCK. PLEASE UPDATE THE DBPR
 WEBSITE OR THE TITLE BLOCKS PRIOR TO RESUBMITTING. FAC
 61G1-16.004(1) & FS 481.2055. (SEE ATTACHED SHEET).
  
 3. SHT A011.01 DETAIL SHOW COMPLIANCE WITH THE
 FOLLOWING:
 A. 11-4.24.3 KNEE CLEARANCE
 B. 11-4.24.4 SINK DEPTH
 C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD APPROACH
 REQUIRED MAX 19" UNDERNEATH THE SINK. - CABINET DOORS
 ARE NOT ALLOWED.)
 D. 11-4.24.6 EXPOSED PIPES & SURFACES
 E. 11-4.24.7 FAUCETS
  
 4. THE SINK IN ROOM 11JO6 SHALL BE ACCESSIBLE. SUBMIT A
 DETAIL SHOWING COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS. (SEE COMMENT 2).
  
 5. SHT P-0.1 DOMESTIC WATER RISER. WATER HAMMER
 ARRESTORS SHALL BE INDICATED AT ALL QUICK CLOSING
 VALVES, (ICE MAKERS & DISH WASHERS). SECTION 604.9.
 WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE
 FIXTURES, IN AN "EFFECTIVE RANGE" NOT IN THE CEILING.
 PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. PLEASE
 SHOW ON THE WATER RISER DIAGRAM.
  
 5. SHT P-0.1 SANITARY RISER DIAGRAM. THE ISLAND VENTS
 SHALL BE INSTALLED PER FIGURE 913.2. (SEE ATTACHED
 SHEET).
  
 6. SHT P-0.1 DETAILS 1, 2 & 3 PER SECTION 504.6.1 A
 VISIBLE AIR GAP OR AIR GAP FITTING IN THE SAME ROOM IS
 REQUIRED. UNDER THE COUNTER IS NOT CONSIDERED VISIBLE.
 PLEASE SHOW COMPLIANCE.--(PER CONVERSATION WITH
 CHRIS HENSON THE INDIRECT WASTE WILL BE VISIBLE WHEN
 CABINET DOOR IS OPEN) 6-29-7
  
 7. SHT P-0.1 THE SANITARY RISER DIAGRAM INDICATES
 GARBAGE DISPOSALS UNDER THE SINKS. ADA APPROVED OFFSET
 GARBAGE DISPOSALS SHALL BE REQUIRED TO KEEP THEM OUT OF
 THE CLEAR FLOOR SPACE REQUIRED FOR THE FIXTURE. PLEASE
 INDICATE THIS REQUIREMENT ON THE PLAN.
  
 8. SHT P-0.1 WATER FILTERS SHALL MEET THE REQUIREMENT
 OF NSF 42. PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE
 FILTERS SHOWING COMPLIANCE. SECTION 611.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved