2007-06-05 16:14:02 | ** UNSAT ** |
| |
| *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR |
| CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW, |
| THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT |
| YET ABLE TO BE MADE. |
| |
| 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE |
| UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER |
| 8TH, 2006. |
| PLEASE THE ARCHITECTURAL SHEETS INDICATE SOME OLDER |
| CODES AS WELL AS THE ELECTRICAL SHEETS WHICH INDICATE |
| SOME OF THE PREVIOUS CODES. SOME OF THE NOTES ON THE |
| ELECTRICAL SHEETS DO INDICATE THE NEWER ADOPTED CODES. |
| |
| 2004 FBC W/2006 REVISIONS (ARCH AND ELECTRICAL SHEETS) |
| 2005 NFPA?70 (NEC) (ARCH AND ELECTRICAL SHEETS) THE |
| OTHER CODES AS LISTED ARE OK. PLEASE BE SURE TO SEE |
| OTHER TRADES FOR COMMENTS ON ANY CODE ADJUSTMENTS. |
| |
| 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON THE |
| TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AND ARCHITECT. |
| PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004 |
| AND FLORIDA STATUTES 481.219 |
| MISSING CERTIFICATE OF AUTHORIZATION NUMBER FOR FIRM, |
| PRINTED NAME OF ARCHITECT AND PRINTED LICENSE NUMBER. |
| ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| TRADES. |
| |
| 3) NOTE: PLEASE SEE THE ARCHITECT DID NOT DATE PLANS |
| WHEN SIGNED AS REQUIRED PER FS 481.221. |
| ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR |
| ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER |
| TRADES. |
| |
| 4) NOTE: PLEASE SEE THE PLANS IN SOME NOTES INDICATE |
| WORK FOR *CARLTON FIELDS* WHICH IS WORK BEING DONE FOR |
| ANOTHER TENANT BUILD-OUT ON ANOTHER FLOOR. REDLINED AT |
| LOCATIONS. |
| PLEASE ADJUST. |
| FBC 106.1.2 |
| |
| 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER HAS BEEN |
| ISSUED/ASSESSED AS 1100, PLEASE INCLUDE ON PLANS AS |
| THERE WILL BE MORE THAN ONE TENANT ON FLOOR WITH MORE |
| THAN ONE SUITE/UNIT. |
| AFC 61G1-16.004 |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 6) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR THE |
| AHA ENGINEERING FIRM DOES NOT COORDINATE WITH THAT AS |
| LISTED WITH THE FLORIDA DEPARTMENT OF BUSINESS AND |
| PROFESSIONAL REGULATION. |
| ** THE ADDRESS OF THE SATELLITE OFFICE IS OK, HOWEVER |
| PLEASE LIST THE PRIMARY HOME OFFICE AS LICENSED. |
| |
| 7) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE SCOPE OF WORK |
| WILL BE UNDER SEPARATE PERMITS. THE PHONE, CATV, ACCESS |
| CONTROL SYSTEM ETC. PERMITS FOR OTHER THAN SECURITY CAN |
| REFERENCE BACK TO THESE PLANS FOR PERMIT HOWEVER THE |
| VALUE AND PERMIT FEE IS BASED ON THAT SCOPE OF WORK. |
| THE ACCESS CONTROL SYSTEM/SECURITY WILL REQUIRE PLANS |
| AND SUBMITTALS FOR DEVICES FOR ACCESS CONTROL. * PLEASE |
| KNOW THAT THESE DEVICES MAY NOT IMPEDED EGRESS FROM |
| BUILDING IN THE EVENT OF AN EMERGENCY PER LS 101 CODE. |
| |
| 8) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY |
| CALCULATIONS SUBMITTED AS THE VERSION ADOPTED AS OF |
| DECEMBER 8TH, 2006 IS NOT THAT AS SUBMITTED. (3.0). |
| PLEASE SEE THE CALCULATIONS NEED TO BE SIGNED BY THE |
| OWNER'S AGENT AS STATED ON SHEETS. (CONTRACTOR). PLEASE |
| COORDINATE ALL OF THE TYPES OF FIXTURES, THE NUMBER OF |
| FIXTURES ON THE CALCULATIONS WITH THAT OF THE FIXTURES |
| ON PLANS AND FIXTURE LEGEND. THERE ARE SOME |
| DISCREPANCIES BETWEEN THE THREE. |
| PLEASE LABEL THE ROOMS ON CALCULATIONS AS THE |
| DESIGNATIONS ON PLANS OR TO THE POINT EACH ROOM WHICH |
| CONTAINS THE SAME NAME OR CURRENTLY THE SAME |
| DESCRIPTION FOR MULTIPLE ROOMS CAN BE DIFFERENTIATED. |
| PLEASE SEE FBC CHAPTER 13 2004 W/2006 REVISIONS |
| 13-415.1.AB.1.1, .1.2, 13-415.2, 13-103.1.1.1 ETC. |
| |
| 9) NOTE: PLEASE SEE THE TRANSFORMER LIST WHICH |
| INDICATES 400AMP OCP ON THE PRIMARY SIDE OF THE T8A |
| WHICH DOES NOT MEET 450.3. PLEASE SEE THAT IF THE |
| TRANSFORMER IS NOT GOING TO BE PART OF THIS BUILDING |
| REMOVE OR CORRECT OCP SIZE. |
| |
| 10) NOTE: PLEASE SEE THE TRANSFORMER LEGEND DOES NOT |
| CORRELATE WITH THAT OF THE RATING OF THE TRANSFORMER |
| INDICATED ON DP1. |
| PLEASE COORDINATE AND ADJUST AS NEEDED. |
| FBC 106.1.2 |
| |
| 11) NOTE: PLEASE SEE THE ELECTRICAL ROOM CONTAINS |
| EQUIPMENT WHICH IS NOT LISTED OR SHOWN ON RISER OR |
| PANEL SCHEDULES SUBMITTED, PLEASE COMPLETE. |
| FBC 106.3.5.1.2, 106.1.2 |
| NEC 215.5, 408.4, 310.16, 240.4 ETC |
| |
| 12) NOTE: PLEASE SEE THE RISER INDICATE THE ELECTRICAL |
| ROOM LOCATED ON THE 10TH FLOOR AND THE PLANS INDICATE |
| THIS ON THE SAME FLOOR AS THE TENANT SPACE?? PLEASE |
| CORRELATE. |
| FBC 106.1.2 |
| |
| 13) NOTE: PLEASE SEE THE EMERGENCY LIGHTING AND EXIT |
| LIGHTS DO NOT MEET 700.12F |
| ALSO INDICATES THESE BEING FED FROM THE EMERGENCY PANEL |
| ON THE 11TH FLOOR, HOWEVER THIS BUILD OUT IS FOR THE |
| 11TH FLOOR. AS THE RISER AND PLANS DO NOT MATCH AND THE |
| CIRCUITING IS NOT CORRECT IT IS UNCLEAR WHAT IS BEING |
| DONE. |
| PLEASE ALSO EXPLAIN THE EMERGENCY LIGHTING DETAIL AS |
| INDICATED ON E1.11. |
| |
| 14) NOTE: PLEASE SEE PANEL L411AS THIS IS A 100AMP |
| RATED PANEL WITH 125AMP BREAKER FEEDING THIS PANEL? |
| PLEASE CLARIFY AND EXPLAIN. |
| FBC 106.1.2, |
| NEC 240, 408,ETC |
| |
| 15) NOTE: PLEASE SEE THE CORRIDORS WHICH ARE BEING |
| SHOWN ON THESE PLANS AS EXISTING DO NOT EXISTING UNDER |
| THE BASE BUILDING AND ARE NOT BEING APPLIED FOR UNDER |
| THE BUILD OUT PERMIT. THIS WAS IN THE CONDITION OF |
| ISSUANCE OF MAIN BUILDING PERMIT AND CONTRACTOR ALONG |
| WITH OWNER SAID THIS WORK WOULD BE PERMITTED BEFORE |
| BUILD OUTS; HOWEVER THIS IS NOT THE CASE. |
| PLEASE SEE FBC 106, 104, 105 FOR WORK REQUIRED TO HAVE |
| PERMITS. |
| |
| 16) NOTE: PLEASE CLARIFY SOME FIXTURES WHICH CONTAIN |
| LETTERING OF SOME KIND WHICH COULD NOT LOCATE |
| DESIGNATIONS OR ANY NOTES FOR WHAT SOME OF THESE ARE. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 17) NOTE: PLEASE SEE THAT ANY CHANGES ON THE BUILD OUT |
| PLANS NEEDS TO BE INCORPORATED INTO THE BASE BUILDING |
| PLANS. PLEASE COORDINATE FOR LOADS, CALCULATIONS, ETC. |
| FBC 106.1.2 |
| |
| 18) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND |
| CORRELATE WITH THE PANEL SCHEDULES. |
| FBC 106.3.5.1.2 |
| |
| 19) NOTE: PLEASE PROVIDE THE MINIMUM LAYOUT FOR ALL FA |
| DEVICES FOR HORNS AND STROBES PER FBC 11-4.28.1,.2 AND |
| .3(4). THE LEVELS ARE INDICATE ON THE SYMBOL LEGEND |
| HOWEVER THE BASE BUILD OUT PLANS ARE REQUIRED TO SHOW |
| THE MINIMUM LOCATIONSFOR FBC COMPLIANCE EVEN IF |
| THOUGH THE FIRE ALARM AND ANY FIRE SPRINKLER PERMITS |
| ARE DONE SEPARATELY AS REQUIRED. |
| FBC 106.3.5.1.2, 106.1.2 |
| |
| 20) NOTE: PLEASE CLARIFY THE ROOM LABELED AS *IT* |
| ROOM.; IF THIS IS INDEED A TRUE IT ROOM AS DEFINED IN |
| THE NEC 645 AND NFPA-75, THEN PLEASE ADJUST PLANS TO |
| MEET THE MINIMUM REQUIREMENTS FOR BUILDING, ELECTRICAL |
| AND ANY MECHANICAL. |
| IF THIS IS NOT A TRUE IT ROOM BY DEFINITIONS, PLEASE |
| REMOVE THIS DESIGNATION FROM PLANS. |
| |
| 21) NOTE: PLEASE SEE NOTES MENTIONS THE MAINSHUNT |
| TRIP RATED SWITCH WILL BE 600AMP RATED YET RISER SHOWS |
| 400AMP. PLEASE CORRELATE. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |