Plan Review Notes
Plan Review Notes For Permit 07050059
Permit Number 07050059
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-05 16:14:02** UNSAT **
  
 *** PLEASE KNOW THAT AS SOME ITEMS ARE NOT SHOWN FOR
 CODE COMPLIANCE AT THIS TIME OR MISSING FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW NOT
 YET ABLE TO BE MADE.
  
 1) NOTE:PLEASE SEE THE CODES AS STATED NEED TO BE
 UPDATED TO CODES ADOPTED BY THE STATE AFTER DECEMBER
 8TH, 2006.
 PLEASE THE ARCHITECTURAL SHEETS INDICATE SOME OLDER
 CODES AS WELL AS THE ELECTRICAL SHEETS WHICH INDICATE
 SOME OF THE PREVIOUS CODES. SOME OF THE NOTES ON THE
 ELECTRICAL SHEETS DO INDICATE THE NEWER ADOPTED CODES.
  
 2004 FBC W/2006 REVISIONS (ARCH AND ELECTRICAL SHEETS)
 2005 NFPA?70 (NEC) (ARCH AND ELECTRICAL SHEETS) THE
 OTHER CODES AS LISTED ARE OK. PLEASE BE SURE TO SEE
 OTHER TRADES FOR COMMENTS ON ANY CODE ADJUSTMENTS.
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON THE
 TITLE BLOCKS FOR THE ARCHITECTURAL FIRM AND ARCHITECT.
 PLEASE SEE THE FLORIDA ADMINISTRATIVE CODE 61G1-16.004
 AND FLORIDA STATUTES 481.219
 MISSING CERTIFICATE OF AUTHORIZATION NUMBER FOR FIRM,
 PRINTED NAME OF ARCHITECT AND PRINTED LICENSE NUMBER.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 3) NOTE: PLEASE SEE THE ARCHITECT DID NOT DATE PLANS
 WHEN SIGNED AS REQUIRED PER FS 481.221.
 ** PLEASE KNOW THIS IS REQUIRED FOR ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS MADE BY OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE THE PLANS IN SOME NOTES INDICATE
 WORK FOR *CARLTON FIELDS* WHICH IS WORK BEING DONE FOR
 ANOTHER TENANT BUILD-OUT ON ANOTHER FLOOR. REDLINED AT
 LOCATIONS.
 PLEASE ADJUST.
 FBC 106.1.2
  
 5) NOTE: PLEASE SEE THE SUITE/UNIT NUMBER HAS BEEN
 ISSUED/ASSESSED AS 1100, PLEASE INCLUDE ON PLANS AS
 THERE WILL BE MORE THAN ONE TENANT ON FLOOR WITH MORE
 THAN ONE SUITE/UNIT.
 AFC 61G1-16.004
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE SEE THE ADDRESS ON TITLE BLOCKS FOR THE
 AHA ENGINEERING FIRM DOES NOT COORDINATE WITH THAT AS
 LISTED WITH THE FLORIDA DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION.
 ** THE ADDRESS OF THE SATELLITE OFFICE IS OK, HOWEVER
 PLEASE LIST THE PRIMARY HOME OFFICE AS LICENSED.
  
 7) NOTE: PLEASE KNOW THAT ALL LOW VOLTAGE SCOPE OF WORK
 WILL BE UNDER SEPARATE PERMITS. THE PHONE, CATV, ACCESS
 CONTROL SYSTEM ETC. PERMITS FOR OTHER THAN SECURITY CAN
 REFERENCE BACK TO THESE PLANS FOR PERMIT HOWEVER THE
 VALUE AND PERMIT FEE IS BASED ON THAT SCOPE OF WORK.
 THE ACCESS CONTROL SYSTEM/SECURITY WILL REQUIRE PLANS
 AND SUBMITTALS FOR DEVICES FOR ACCESS CONTROL. * PLEASE
 KNOW THAT THESE DEVICES MAY NOT IMPEDED EGRESS FROM
 BUILDING IN THE EVENT OF AN EMERGENCY PER LS 101 CODE.
  
 8) NOTE: PLEASE VERIFY THE VERSION OF THE ENERGY
 CALCULATIONS SUBMITTED AS THE VERSION ADOPTED AS OF
 DECEMBER 8TH, 2006 IS NOT THAT AS SUBMITTED. (3.0).
 PLEASE SEE THE CALCULATIONS NEED TO BE SIGNED BY THE
 OWNER'S AGENT AS STATED ON SHEETS. (CONTRACTOR). PLEASE
 COORDINATE ALL OF THE TYPES OF FIXTURES, THE NUMBER OF
 FIXTURES ON THE CALCULATIONS WITH THAT OF THE FIXTURES
 ON PLANS AND FIXTURE LEGEND. THERE ARE SOME
 DISCREPANCIES BETWEEN THE THREE.
 PLEASE LABEL THE ROOMS ON CALCULATIONS AS THE
 DESIGNATIONS ON PLANS OR TO THE POINT EACH ROOM WHICH
 CONTAINS THE SAME NAME OR CURRENTLY THE SAME
 DESCRIPTION FOR MULTIPLE ROOMS CAN BE DIFFERENTIATED.
 PLEASE SEE FBC CHAPTER 13 2004 W/2006 REVISIONS
 13-415.1.AB.1.1, .1.2, 13-415.2, 13-103.1.1.1 ETC.
  
 9) NOTE: PLEASE SEE THE TRANSFORMER LIST WHICH
 INDICATES 400AMP OCP ON THE PRIMARY SIDE OF THE T8A
 WHICH DOES NOT MEET 450.3. PLEASE SEE THAT IF THE
 TRANSFORMER IS NOT GOING TO BE PART OF THIS BUILDING
 REMOVE OR CORRECT OCP SIZE.
  
 10) NOTE: PLEASE SEE THE TRANSFORMER LEGEND DOES NOT
 CORRELATE WITH THAT OF THE RATING OF THE TRANSFORMER
 INDICATED ON DP1.
 PLEASE COORDINATE AND ADJUST AS NEEDED.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE THE ELECTRICAL ROOM CONTAINS
 EQUIPMENT WHICH IS NOT LISTED OR SHOWN ON RISER OR
 PANEL SCHEDULES SUBMITTED, PLEASE COMPLETE.
 FBC 106.3.5.1.2, 106.1.2
 NEC 215.5, 408.4, 310.16, 240.4 ETC
  
 12) NOTE: PLEASE SEE THE RISER INDICATE THE ELECTRICAL
 ROOM LOCATED ON THE 10TH FLOOR AND THE PLANS INDICATE
 THIS ON THE SAME FLOOR AS THE TENANT SPACE?? PLEASE
 CORRELATE.
 FBC 106.1.2
  
 13) NOTE: PLEASE SEE THE EMERGENCY LIGHTING AND EXIT
 LIGHTS DO NOT MEET 700.12F
 ALSO INDICATES THESE BEING FED FROM THE EMERGENCY PANEL
 ON THE 11TH FLOOR, HOWEVER THIS BUILD OUT IS FOR THE
 11TH FLOOR. AS THE RISER AND PLANS DO NOT MATCH AND THE
 CIRCUITING IS NOT CORRECT IT IS UNCLEAR WHAT IS BEING
 DONE.
 PLEASE ALSO EXPLAIN THE EMERGENCY LIGHTING DETAIL AS
 INDICATED ON E1.11.
  
 14) NOTE: PLEASE SEE PANEL L411AS THIS IS A 100AMP
 RATED PANEL WITH 125AMP BREAKER FEEDING THIS PANEL?
 PLEASE CLARIFY AND EXPLAIN.
 FBC 106.1.2,
 NEC 240, 408,ETC
  
 15) NOTE: PLEASE SEE THE CORRIDORS WHICH ARE BEING
 SHOWN ON THESE PLANS AS EXISTING DO NOT EXISTING UNDER
 THE BASE BUILDING AND ARE NOT BEING APPLIED FOR UNDER
 THE BUILD OUT PERMIT. THIS WAS IN THE CONDITION OF
 ISSUANCE OF MAIN BUILDING PERMIT AND CONTRACTOR ALONG
 WITH OWNER SAID THIS WORK WOULD BE PERMITTED BEFORE
 BUILD OUTS; HOWEVER THIS IS NOT THE CASE.
 PLEASE SEE FBC 106, 104, 105 FOR WORK REQUIRED TO HAVE
 PERMITS.
  
 16) NOTE: PLEASE CLARIFY SOME FIXTURES WHICH CONTAIN
 LETTERING OF SOME KIND WHICH COULD NOT LOCATE
 DESIGNATIONS OR ANY NOTES FOR WHAT SOME OF THESE ARE.
 FBC 106.1.2, 106.3.5.1.2
  
 17) NOTE: PLEASE SEE THAT ANY CHANGES ON THE BUILD OUT
 PLANS NEEDS TO BE INCORPORATED INTO THE BASE BUILDING
 PLANS. PLEASE COORDINATE FOR LOADS, CALCULATIONS, ETC.
 FBC 106.1.2
  
 18) NOTE: PLEASE COMPLETE CIRCUITING ON PLANS AND
 CORRELATE WITH THE PANEL SCHEDULES.
 FBC 106.3.5.1.2
  
 19) NOTE: PLEASE PROVIDE THE MINIMUM LAYOUT FOR ALL FA
 DEVICES FOR HORNS AND STROBES PER FBC 11-4.28.1,.2 AND
 .3(4). THE LEVELS ARE INDICATE ON THE SYMBOL LEGEND
 HOWEVER THE BASE BUILD OUT PLANS ARE REQUIRED TO SHOW
 THE MINIMUM LOCATIONSFOR FBC COMPLIANCE EVEN IF
 THOUGH THE FIRE ALARM AND ANY FIRE SPRINKLER PERMITS
 ARE DONE SEPARATELY AS REQUIRED.
 FBC 106.3.5.1.2, 106.1.2
  
 20) NOTE: PLEASE CLARIFY THE ROOM LABELED AS *IT*
 ROOM.; IF THIS IS INDEED A TRUE IT ROOM AS DEFINED IN
 THE NEC 645 AND NFPA-75, THEN PLEASE ADJUST PLANS TO
 MEET THE MINIMUM REQUIREMENTS FOR BUILDING, ELECTRICAL
 AND ANY MECHANICAL.
 IF THIS IS NOT A TRUE IT ROOM BY DEFINITIONS, PLEASE
 REMOVE THIS DESIGNATION FROM PLANS.
  
 21) NOTE: PLEASE SEE NOTES MENTIONS THE MAINSHUNT
 TRIP RATED SWITCH WILL BE 600AMP RATED YET RISER SHOWS
 400AMP. PLEASE CORRELATE.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-06-04 21:14:55IN ELEC FOR REVIEW