2007-05-07 14:47:53 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PER FBC-2004, CHAPTER 1, SECTION |
| 106.1.3, QUALITY OF BUILDING PLANS: THE |
| BUILDING OFFICIAL MAY ESTABLISH THROUGH DEPARTMENTAL |
| POLICY, STANDARDS FOR PLANS |
| AND SPECIFICATIONS, IN ORDER TO PROVIDE |
| CONFORMITY TO ITS RECORD RETENTION |
| PROGRAM. THIS POLICY MAY INCLUDE SUCH |
| THINGS AS MINIMUM SIZE, SHAPE, CONTRAST, |
| CLARITY, OR OTHER ITEMS RELATED TO |
| RECORDS MANAGEMENT. |
| NOTE: PLEASE CLEARLY INDICATE THE POOL HEATERS LOCATION |
| ON THE RESUBMITTED DRAWINGS. |
| |
| 2. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: PLEASE INDICATE THE CORRESPONDING LENGTHS OF THE |
| CUT SECTIONS OF PIPE ON THE RESUBMITTAL TO VERIFY THE |
| LONGEST LENGTH OF THE SYSTEM. |
| |
| 3. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON |
| THE RESUBMITTED DRAWINGS. |
| |
| 4. PLEASE SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, SHOWING LISTINGS FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), BTU |
| LOAD, AND THE FBC-2004 FUEL GAS CODE SEC 402.2. |
| |
| A} MP REGULATORS |
| B} GAS RANGE |
| C} DRYER |
| D}WATER HEATER |
| |
| 5. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE INDICATE |
| THE SHUTOFF VALVE ON THE RESUBMITTAL. |
| |
| 6. PER FBC-2004 FUEL GAS, SECTION 404.13.3AN |
| INSULATED COPPER TRACER WIRE SHALL BE INSTALLED |
| ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE |
| TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE |
| INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. |
| PLEASE INDICATE THE TRACER WIRE ON THE RESUBMITTAL. |
| |
| 7. SUBMIT CALCULATIONS FOR COMBUSTION |
| AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| GAS CODE SECTION 304. |
| |
| 8. SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMINATION OF THE |
| GAS VENTS PER FBC-2004 FUEL GAS CODE |
| SECS. 502 THRU 505. |
| |
| 9. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |