Plan Review Notes
Plan Review Notes For Permit 07050010
Permit Number 07050010
Review Stop G
Sequence Number 1
Notes
Date Text
2007-05-07 11:56:29****************PROVISO*****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 B} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  
 C} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT TRAP
 SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT SHUTOFF
 VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.