2007-05-08 08:35:50 | *** DENIED *** |
| 1) MANUFACTURER'S SPECIFICATION'S WERE SUBMITTED, |
| PLEASE ALSO SUBMIT MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. |
| |
| 2) PLEASE SHOW ON SURVEY, LOCATION OF GENERATOR, AND |
| DISTANCE TO HOUSE, WINDOWS AND OTHER BUILDING OPENINGS |
| WITHIN FIVE FEET. |
| |
| *** INFORMATIONAL: PER 2004 FBC, FUEL GAS - POWERED |
| EQUIPMENT - PERMANENTLY INSTALLED EQUIPMENT POWERED BY |
| INTERNAL COMBUSTION ENGINES SHALL BE INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS AND NFPA 37. |
| NFPA 37 INSTALLATION & USE OF STATIONARY COMBUSTION |
| ENGINES & GAS TURBINES: 4.1.4ENGINES (GENERATORS) |
| LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT FROM OPENINGS |
| IN WALLS & AT LEAST 5 FT FROM STRUCTURES HAVING |
| COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT REQUIRED |
| WHEN |
| (1) THE ADJACENT WALL HAS A MINIMUM FIRE RESISTANCE |
| RATING OF 1 HOUR OR (2) THE WEATHERPROOF ENCLOSURE IS |
| CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, AND IT HAS |
| BEEN DEMONSTRATED THAT A FIRE WITHIN THE ENCLOSURE WILL |
| NOT IGNITE COMBUSTIBLE MATERIALS OUTSIDE THE ENCLOSURE. |
| INFORMATIVE: A.8.2.3.1EXHAUST SYSTEMS SHOULD NOT |
| TERMINATE UNDER STRUCTURES OR WHERE THE EXHAUST MIGHT |
| BE DRAWN INTO THE VENTILATION INTAKES. |
| 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS |
| LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE |
| TERMINATION POINT SHALL BE LOCATED AT LEAST 3 FT FROM |
| THE ROOF STRUCTURE. |
| PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL |
| EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, |
| GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED |
| CLEARANCES TO THE ADJACENT |
| PROPERTY STRUCTURES, I.E. FENCE, BUILDING, WINDOWS, |
| DOORS, OR OPENINGS. |
| FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES AROUND |
| EQUIPMENT FOR SERVICING,AND PROVIDE MANUFACTURER'S |
| INSTALLATION INSTRUCTIONS AT THE JOB-SITE FOR THE FIELD |
| INSPECTOR. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |