2007-05-24 11:13:22 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: NOT ALL CUT SECTIONS OF PIPE HAVE CORRESPONDING |
| LENGTH INDICATED ON THE DRAWING. THIS INCLUDES ABOVE |
| GROUND, UNDERGROUND AND EXISTING PIPING. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: PLEASE INDICATE THE ABOVE GROUND PIPING |
| MATERIAL. |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| NOTE: NEED TO INDICATE THE EXISTING HOUSE BTU LOAD AS |
| WELL AS THE PROPOSED GENERATOR. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: NEED TO INDICATE THE EXISTING PIPING |
| CORRESPONDING LENGTHS TO VERIFY THIS. |
| |
| 5. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| LP GAS SPECIFY 10 PSI, 2 PSI, OR 11 INCH WC. |
| |
| 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 |
| NOTE: PLEASE SUBMIT MANUFACTURER SHEETS OF SECOND STAGE |
| REGULATOR TO THE PROPOSED GENERATOR INDICATING NAME OF |
| MANUFACTURER, REGULATOR CAPACITY (LARGEST AMOUNT OF |
| BTU'S SERVED BY REGULATOR), AND SHOW A LISTING FROM A |
| NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL). SUBMIT |
| MANUFACTURER INSTALLATION INSTRUCTIONS TO VERIFY SET |
| BACKS TO STRUCTURES. |
| |
| 7. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| NOTE: THIS INCLUDES EXISTING AS WELL AS PROPOSED |
| TANKS. |
| |
| 8. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 3-2.2.7(H). |
| NOTE: THIS INCLUDES EXISTING AS WELL AS PROPOSED |
| TANKS. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |