Plan Review Notes For Permit 07041005 |
Permit Number |
07041005 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-14 10:00:50 | *****APPROVED*****W/ REMINDER | | | | | | PLAN SHEET FP1 OF FP1 STAMPED, INITIALED, AND DATED; | | READY FOR PERMIT ISSUANCE. | | | | | | THE ADDITION OR MODIFICATION OF THE SPRINKLER SYSTEM | | SHALL BE HYDROSTATICALLY TESTED AT 200 PSI FOR TWO (2) | | HOURS;HOWEVER IF THE MODIFICATION CANNOT BE ISOLATED | | AS PER EXCEPTION INNFPA 13 - 2002 EDITION,PLEASE | | SUBMIT AT THE TIME OF INSPECTION ON YOUR OFFICIAL | | LETTERHEAD:THE LOCATION OF THE SCOPE OF WORK, THE | | PERMIT NUMBER, THE CODE REFERENCE AND LANGUAGE,TO BE | | FILED BY WPB FIRE PREVENTION. |
|