Plan Review Notes For Permit 07040934 |
Permit Number |
07040934 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2008-06-05 16:01:07 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | **REVISION TO MECH. PLAN, COOLING LOAD CAL'S. AND | | E-CAL'S.** | | *** DENIED *** | | | | 1) THE PLANS NEED TO BE SEALED BY THE ARCHITECT, PER | | FAC 61G1-16.003. | | | | 2) ONE OF THE MECHANICAL PLANS IS A PHOTO COPY, PLEASE | | SUBMIT TWO SIGNED AND SEALED MECHANICAL PLANS. | | | | 3) ELECTRICAL AND PLUMBING PLANS MAY NEED TO BE | | REVISED, PLEASE CHECK WITH THOSE REVIEWERS. | | | | ** THE REVISED ENERGY CAL'S ARE NOT REQUIRED FOR THE | | MECHANICAL REVISION, BUT MAY BE FOR OTHER TRADE | | REVIEWERS, PLEASE CHECK WITH BUILD. ELECT. AND PLUMB. | | REVIEWERS. | | | | *** REVISED COOLING LOAD CALCULATIONS WERE REVIEWED AND | | STAMPED, ONE SET WAS RETURNED WITH APPLICATION. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] |
|