Date Text
2007-05-07 14:48:03PLANS ROUTED BACK TO LUIS M.
2007-05-07 14:47:26 
 ** UNSAT **
  
  
 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH
 ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS
 UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED
 FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS
 NOT MADE BY OTHER TRADE(S).
  
 2) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS UNDER THE
 2004 FBC W/2006 REVISIONS. PER 13-415.1.AB.1.1,
 13-415.2
 PLEASE SEE THE 2006 REVISIONS FOR CHANGES IN CHAPTER 13
 FROM THE 2004 FBC W/2005 REVISIONS.
  
 3) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR WATER HEATER
 IS TO BE SHOWN AND FIGURED AT 125%. (CHANGED FROM
 PREVIOUS CODE).
  
 4) NOTE: PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF
 WORK HAS NOW DECREASED TO ABOUT HALF AS PREVIOUSLY
 SUBMITTED?? PLEASE VERIFY AS VALUE MUST INCLUDE ALL
 LABOR AND MATERIALS EVEN IF MATERIALS OR ANY
 PERMANENTLY INSTALLED EQUIPMENT IS OWNER SUPPLIED.
 FBC 108.3
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]