Notes
Date Text
2007-05-12 17:03:25 
  
 DENIED
  
 1)DESIGN PRESSURE IN THE 2004 FBC HAVE BEEN UPDATED
 WITH THE 2006 AMENDMENTS, ANY BUILDING IN A NORMALLY
 EXPOSURE BCATEGORY THAT HAS OPEN TERRAIN (INCLUDES
 BODIES OF WATER, GOLF COURSES, ETC) IN ANY QUADRANT FOR
 A DISTANCE OF 600 FT WILL BE CONSIDERED EXPOSURE C.
  
 2)SHUTTER PERMIT APPLICATIONS REQUIRE A KEY PLAN,
 SHUTTER SCHEDULE CLEARLY MARKED WITH THE INFORMATION
 SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION, MOUNTING
 CONNECTION TYPE, ANCHOR TYPE, ETC.) PLEASE SEE THE
 ATTACHED UPDATED SCHEDULE AND THE DRAWINGS THAT ARE
 PART OF THE PRODUCT APPROVALS TO CORRESPOND WITH THE
 SCHEDULE. ****** PLEASE SEE THAT THE DRAWINGS HAVE MANY
 ITEMS NOT ON SCHEDULE CIRCLED, INCREASES FOR EXPOSURE C
 WILL NOT REACH SPANS REQUIRED,CONNECTION TYPES CHOSEN
 DO NOT MATCH ANCHOR SPACING AND TAPCONS, EDGE DISTANCE
 CIRCLED DO NOT MATCH SCHEDULE. *******
  
 3)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 4)PROVIDE PROOF OF OWNERSHIP OWNER STATUS IN SYSTEM
 DIFFERS FROM PAPA
  
 BLDG PLAN REVIEW