Plan Review Notes
Plan Review Notes For Permit 07040808
Permit Number 07040808
Review Stop G
Sequence Number 1
Notes
Date Text
2007-05-02 13:19:15DENIED
 REFERENCE:
 ** FBC-2004 FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE SUBMITTED ISOMETRIC DOES NOT INDICATE THE
 CORRESPONDING LENGTHS OF THE CUT SECTIONS OF PIPE OF
 THE PROPOSED GENERATOR GAS PIPING. PLEASE DO THIS ON
 THE RESUBMITTAL TO VERIFY THE INDICATED TOTAL DEVELOPED
 LENGTH OF THIRTY SIX FEET (36'). IS THE TOTAL DEVELOPED
 LENGTH OF THIRTY SIX FEET (36') FOR THE PROPOSED
 GENERATOR OR FOR THE EXISTING SYSTEM. PLEASE CLARIFY ON
 THE RESUBMITTAL.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: NOT ALL PIPE SIZES ARE INDICATED ON THE
 ISOMETRIC. THE PIPING OUT OF THE METER SHOULD BE SIZED
 1-1/4".PLEASE DO THIS ON THE RESUBMITTAL.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 NOTE: PLEASE CLEARLY INDICATE THE LONGEST LENGTH OF THE
 EXISTING SYSTEM AND THE PROPOSED SYSTEM TO VERIFY HOW
 SYSTEM IS TO BE SIZED.
  
 4. PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
 NOTE: PLEASE INDICATE THIS ON THE RESUBMITTAL FOR THE
 UNDERGROUND PE.
  
 5. PER FBC-2004 FUEL GAS SECTION 409.5 EQUIPMENT
 SHUTOFF VALVE: EACH APPLIANCE SHALL BE PROVIDED WITH A
 SHUTOFF VALVE SEPERATE FROM THE APPLIANCE. THE SHUTOFF
 VALVE SHALL BE LOCATED IN THE SAME ROOM AS THE
 APPLIANCE, NOT FURTHER THAN 6 FEET FROM THE APPLIANCE,
 AND SHALL BE INSTALLED UPSTREAM FROM THE UNION,
 CONNECTOR OR QUICK DISCONNECT DEVICE IT SERVES. SUCH
 SHUTOFF VALVES SHALL BE PROVIDED WITH ACCESS. NOTE:
 PLEASE INDICATE A SHUTOFF VALVE FOR THE PROPOSED
 GENERATOR ON THE RESUBMITTAL.
  
 6. A GAS PERMIT CAN NOT BE ISSUED UNTIL
 A GEN/RES PERMIT APPLICATION HAS BEEN
 APPLIED FOR AND APPROVED BY ZONING FOR
 THE GENERATOR LOCATION.
  
 END OF COMMENTS:
  