Plan Review Notes
Plan Review Notes For Permit 07040806
Permit Number 07040806
Review Stop ENG
Sequence Number 1
Notes
Date Text
2007-04-26 09:36:00FAILED FOR FOLLOWING REASONS:
 1. NEED TO GET ROW APPROVAL FROM WINDEL PALMER, 45TH
 STREET, ENGINEERING DEPT.
 2. WHAT ARE THE CHANGES IN DRAINAGE STRUCTURE FROM
 EXISTING TO NEW? ARE YOU CHANGING IN WATER QUALITY? MAY
 NEED WATER QUALITY CALCULATION,PRE AND POST
 CONDITION PER SFWMD.
 3. NEED APPROVAL FROM DRAINAGE DISTRICT FOR THAT
 CANAL.
 4. PLEASE SHOW THE DETAIL OF EXISTING AND NEW DRAINAGE
 STRUCTURE, LIKE BLEEDING ELEVATION, WEIR ELEVATION
 ETC.,ETC.,
  
 PLEASE RESPOND EACH ITEM TO EXPEDITE THE PERMITTING
 PROCESS.
  
 RASIK CHOKSHI 805-6723