2007-07-27 13:11:00 | *** UNSAT3RD REVIEW *** |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL |
| REMAIN. |
| |
| 1) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS |
| REVIEW, PLEASE COMPLY WITH FBC CHAPTER 13 FOR LIGHTING |
| CONTROLS.ALL NEW BEING INSTALLED NEEDS TO COMPLY. |
| THIS TENANT SPACE IS NOT DEFINED AS A BUILDING AND THIS |
| SPACE IS LOCATED IN A BUILDING GREATER THAN 5K SQ FT. |
| THE RESPONSE MENTIONS THIS IS 2400 + SQ FT AND DOES NOT |
| NEED LIGHTING CONTROLS. THIS IS NOT THE CASE.PLEASE |
| SEE THE DEFINITIONS OF A BUILDING IN BOTH CHAPTER 13 |
| AND FBC DEFINITIONS. TENANT OCCUPANCIES LOCATED IN A |
| BUILDING OVER 5K SQ FT EVEN IF 200 SQ FT FOR EXAMPLE |
| FOR THE INDIVIDUAL TENANT SPACE STILL REQUIRES LIGHTING |
| CONTROLS FOR AUTOMATED SHUTTING OFF/TURNING OFF OF |
| LIGHTS. |
| THIS HAS BEEN CONFIRMED WITH THE STATE ON MANY |
| OCCASIONS AND THE STATE TAC COMMITTEE WHEN THE CODE |
| CHANGE WAS MADE ALMOST TWO EARS AGO. |
| PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE CONFIRMED |
| AND DO NOT CORRELATE FOR LIGHTING CONTROLS AND PLANS. |
| 13-415.1.ABC.1.1, .1.2, 13-415.1.A, 13-415.2 |
| 13-101. |
| |
| 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED THE |
| ADDRESS OF THE UNIT OR SUITE NUMBER TO BE ADDED TO THE |
| PLANS, HOWEVER THE RESPONSE MENTIONS THIS ENTIRE |
| BUILDING IS ONE TENANT. |
| PLEASE SEE THE ENERGY CALCULATIONS WHICH WERE SUBMITTED |
| BY THE ARCHITECT STATES A UNIT/SUITE OF #118? |
| PLEASE CLARIFY HOW THIS IS POSSIBLE. |
| |
| 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE |
| NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT |
| COMMENTS FOR CODE COMPLIANCE. |
| PLEASE SEE A FEE HAS NOW BEEN ASSESSED TO THE DESIGN |
| PROFESSIONAL AS REQUIRED PER THE ABOVE FLORIDA STATUTE. |
| THIS FEE OF $1800.00 IS DUE BEFORE PLANS CAN BE |
| RESUBMITTED. |
| ONE COPY OF ELECTRICAL PLANS ALONG WITH ONE COPY OF |
| ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE. |
| TO DATE NO ONE HAS CONTACTED THIS REVIEWER TO GO OVER |
| ANY OF THE COMMENTS. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |