2007-07-27 13:11:00*** UNSAT3RD REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW STILL
 REMAIN.
  
 1) NOTE: PLEASE SEE AS REQUESTED ON THE PREVIOUS
 REVIEW, PLEASE COMPLY WITH FBC CHAPTER 13 FOR LIGHTING
 CONTROLS.ALL NEW BEING INSTALLED NEEDS TO COMPLY.
 THIS TENANT SPACE IS NOT DEFINED AS A BUILDING AND THIS
 SPACE IS LOCATED IN A BUILDING GREATER THAN 5K SQ FT.
 THE RESPONSE MENTIONS THIS IS 2400 + SQ FT AND DOES NOT
 NEED LIGHTING CONTROLS. THIS IS NOT THE CASE.PLEASE
 SEE THE DEFINITIONS OF A BUILDING IN BOTH CHAPTER 13
 AND FBC DEFINITIONS. TENANT OCCUPANCIES LOCATED IN A
 BUILDING OVER 5K SQ FT EVEN IF 200 SQ FT FOR EXAMPLE
 FOR THE INDIVIDUAL TENANT SPACE STILL REQUIRES LIGHTING
 CONTROLS FOR AUTOMATED SHUTTING OFF/TURNING OFF OF
 LIGHTS.
 THIS HAS BEEN CONFIRMED WITH THE STATE ON MANY
 OCCASIONS AND THE STATE TAC COMMITTEE WHEN THE CODE
 CHANGE WAS MADE ALMOST TWO EARS AGO.
 PLEASE SEE THE ENERGY CALCULATIONS CAN NOT BE CONFIRMED
 AND DO NOT CORRELATE FOR LIGHTING CONTROLS AND PLANS.
 13-415.1.ABC.1.1, .1.2, 13-415.1.A, 13-415.2
 13-101.
  
 2) NOTE: PLEASE SEE THE PREVIOUS REVIEW REQUESTED THE
 ADDRESS OF THE UNIT OR SUITE NUMBER TO BE ADDED TO THE
 PLANS, HOWEVER THE RESPONSE MENTIONS THIS ENTIRE
 BUILDING IS ONE TENANT.
 PLEASE SEE THE ENERGY CALCULATIONS WHICH WERE SUBMITTED
 BY THE ARCHITECT STATES A UNIT/SUITE OF #118?
 PLEASE CLARIFY HOW THIS IS POSSIBLE.
  
 3) NOTE: PLEASE SEE THE PREVIOUS REVIEW NOTES GAVE
 NOTICE TO FS 553.80(2)(B) WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 PLEASE SEE A FEE HAS NOW BEEN ASSESSED TO THE DESIGN
 PROFESSIONAL AS REQUIRED PER THE ABOVE FLORIDA STATUTE.
 THIS FEE OF $1800.00 IS DUE BEFORE PLANS CAN BE
 RESUBMITTED.
 ONE COPY OF ELECTRICAL PLANS ALONG WITH ONE COPY OF
 ENERGY CALCULATIONS ARE BEING RETAINED BY THIS OFFICE.
 TO DATE NO ONE HAS CONTACTED THIS REVIEWER TO GO OVER
 ANY OF THE COMMENTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]