Date |
Text |
2007-06-18 11:16:08 | |
| |
| *** UNSAT 2ND REVIEW *** |
| |
| ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS ARE STILL |
| IN NEED OF ADDRESSING. |
| ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS |
| SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW |
| COMMENTS ON RE-SUBMITTAL OF PLANS. |
| |
| 1) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE |
| FBC HAS NOT BEEN ADDRESSED. THE REQUIRED LIGHTING |
| CONTROLS AS PREVIOUSLY NOTED HAVE NOT BEEN PLACED ON |
| PLANS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE |
| NOT CORRECT. THE FIXTURES DO NOT CORRELATE, THE TYPES, |
| THE CONTROLS ETC. |
| PLEASE SEE ALL OF CHAPTER AND THE SECTIONS AS |
| PREVIOUSLY GIVEN. |
| 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1, |
| 13-415.2, 13-415.2.ABC.1.2 |
| |
| 2) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WHICH |
| STATED THE MISSING REQUIRED INFORMATION ON TITLE BLOCKS |
| PER 61G1-16.004. (STILL MISSING THE PRINTED LICENSE |
| NUMBER OF THE ARCHITECT). |
| |
| 3) NOTE: PLEASE SEE THE CIRCUITING MAY NOT ONLY USE |
| LIGHTING, RECEPTACLES ETC. THESE NEED TO BE SPECIFIC TO |
| ROOMS, AREAS, OR OTHER TYPE OF DESIGNATION. MAY USE A |
| NUMERICAL DESIGNATION TO OFFICES OR OTHER LOCATIONS. |
| PLEASE SEE 408.4 |
| |
| 4) NOTE: PLEASE SEE ADDRESS ONLY INDICATES THE |
| LOCATION. THIS BUILDING CONTAINS MORE THAN ONE |
| SUITE/UNIT NUMBER? IF SO PLEASE SEE THE PERMIT |
| APPLICATION NEEDS TO STATE THE SUITE/UNIT ALONG WITH |
| THE PLANS. |
| |
| 5) NOTE: PLEASE SEE MISPRINT FOR NEW PANEL L1C, WHICH |
| IS SHOWN AS LC1 ON PANEL AND L1C ON RISER. |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE SEE FS 553.802B WITH RESPECT TO REPEAT |
| COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A NOTICE |
| GIVEN AT THIS TIME. |
| |
| ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |