Plan Review Notes
Plan Review Notes For Permit 07040753
Permit Number 07040753
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-18 11:16:08 
  
 *** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS FROM THE PREVIOUS ARE STILL
 IN NEED OF ADDRESSING.
 ** PLEASE KNOW AS NOT ALL INFORMATION NEEDED WAS
 SUBMITTED FOR A CODE COMPLIANT REVIEW THERE MAY BE NEW
 COMMENTS ON RE-SUBMITTAL OF PLANS.
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH CHAPTER 13 OF THE
 FBC HAS NOT BEEN ADDRESSED. THE REQUIRED LIGHTING
 CONTROLS AS PREVIOUSLY NOTED HAVE NOT BEEN PLACED ON
 PLANS. PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE
 NOT CORRECT. THE FIXTURES DO NOT CORRELATE, THE TYPES,
 THE CONTROLS ETC.
 PLEASE SEE ALL OF CHAPTER AND THE SECTIONS AS
 PREVIOUSLY GIVEN.
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2, 13-415.2.ABC.1.2
  
 2) NOTE: PLEASE SEE NOTE #3 FROM PREVIOUS REVIEW WHICH
 STATED THE MISSING REQUIRED INFORMATION ON TITLE BLOCKS
 PER 61G1-16.004. (STILL MISSING THE PRINTED LICENSE
 NUMBER OF THE ARCHITECT).
  
 3) NOTE: PLEASE SEE THE CIRCUITING MAY NOT ONLY USE
 LIGHTING, RECEPTACLES ETC. THESE NEED TO BE SPECIFIC TO
 ROOMS, AREAS, OR OTHER TYPE OF DESIGNATION. MAY USE A
 NUMERICAL DESIGNATION TO OFFICES OR OTHER LOCATIONS.
 PLEASE SEE 408.4
  
 4) NOTE: PLEASE SEE ADDRESS ONLY INDICATES THE
 LOCATION. THIS BUILDING CONTAINS MORE THAN ONE
 SUITE/UNIT NUMBER? IF SO PLEASE SEE THE PERMIT
 APPLICATION NEEDS TO STATE THE SUITE/UNIT ALONG WITH
 THE PLANS.
  
 5) NOTE: PLEASE SEE MISPRINT FOR NEW PANEL L1C, WHICH
 IS SHOWN AS LC1 ON PANEL AND L1C ON RISER.
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE FS 553.802B WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A NOTICE
 GIVEN AT THIS TIME.
  
 ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH
 MAY AFFECT THE ELECTRICAL PLANS OR DESIGN OF PROJECT.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved