Plan Review Notes
Plan Review Notes For Permit 07040753
Permit Number 07040753
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-25 14:34:18*** DENIED ***
 1) ENERGY CALCULATIONS ARE CALLING FOR A 92,000 BTU A/C
 SYSTEM, MECHANICAL PLANS ARE CALLING FOR A 30,000 BTU
 A/C SYSTEM, THE TWO MUST COINCIDE, PLEASE CORRECT.
  
 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 76,810
 TOTAL BTU'S, MECHANICAL PLANS ARE CALLING FOR 30,000
 TOTAL BTU'S. SEE 2004 FBC 13--407.1.ABC.1.1, PLEASE
 CORRECT.
  
 3) PLEASE SHOW OUTDOOR AIR CALCULATIONS ON MECHANICAL
 PLANS, SEE 2004 FBC/M 403.3.
  
 4) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT
 ALSO, PER 2004 FBC 13-400.3.ABC.2.
  
 5) COULD NOT FIND THE A/C SYSTEM IN THE EQUIPMENT SPEC.
 LISTED ON THE ARI DIRECTORY WEB SITE. PLEASE SUBMIT
 DETAILED MANUFACTURER'S SPECIFICATION'S AND
 INSTALLATION INSTRUCTIONS FOR A/C SYSTEM BEING
 INSTALLED..
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.