2007-05-14 11:19:13*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS
 TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE -
 SHALL BE REFERENCED.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS
 NECESSARY FOR SAFE OPERATION.
  
 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR WALLS AND
 CEILINGS AS CLASS A, CLASS B, OR CLASS C.
  
 6.ON DRAWING E1.04,AMEND FIRE ALARM SYSTEM NOTE #17
 TO INDICATE THAT DUCT SMOKE DETECTORS SHALL INITIATE A
 GENERAL FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED
  
  