Plan Review Notes For Permit 07040753 |
Permit Number |
07040753 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-05-14 11:19:13 | *****DENIED***** | | | | | | 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS | | TO BE CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH | | SUBMITTED PLAN SHEET. | | | | 2.THE 2003 EDITION OF NFPA 101 - LIFE SAFETY CODE - | | SHALL BE REFERENCED. | | | | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY AS | | NECESSARY FOR SAFE OPERATION. | | | | 5.SPECIFY THE INTERIOR FINISH MATERIALS FOR WALLS AND | | CEILINGS AS CLASS A, CLASS B, OR CLASS C. | | | | 6.ON DRAWING E1.04,AMEND FIRE ALARM SYSTEM NOTE #17 | | TO INDICATE THAT DUCT SMOKE DETECTORS SHALL INITIATE A | | GENERAL FIRE ALARM. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | LETTER INDICATING HOW/WHERE EACH COMMENT WAS ADDRESSED | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|