Date |
Text |
2007-04-30 15:21:42 | ** UNSAT ** |
| |
| ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1 |
| ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF |
| WEST PALM BEACH. |
| |
| |
| 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| AFFECT DESIGNS FOR ALL TRADES. |
| PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| REVIEWER AT A MINIMUM. |
| 2004 FBC W/ 2006 REVISIONS |
| 2005 NFPA-70 |
| |
| 2) NOTE: PLEASE SEE 2004 FBC CHAPTER 13 W/ 2006 |
| REVISIONS. |
| PLEASE SEE MISSING LIGHTING CONTROLS PER |
| 13-415.1.ABC.1.1, .1.2. A LIGHTING CONTACTOR IS |
| INDICATED, HOWEVER NO TIMES SCHEDULING, NO TIME OVER |
| RIDES, ETC ARE SHOWN. |
| PLEASE SEE THE WRONG EDITION OF THE FLORIDA ENERGY CODE |
| IS SHOWN AND CALCULATED. |
| PLEASE CORRELATE THE LIGHTING AS SHOWN ON PLANS WITH |
| THAT OF THE FIXTURES, WATTAGES ETC AS SHOWN ON |
| CALCULATIONS. |
| PLEASE SEE THE CONTROL FOR LIGHTING NEEDS TO COORDINATE |
| WITH THE METHOD ON PLANS. |
| PLEASE SEE 13-415.ABC.1.2 |
| PLEASE BE SURE THAT ANY OVER RIDE DEVICES ARE SHOWN ON |
| PLANS AND SYMBOL LEGEND. |
| PLEASE BE SURE THE ENERGY CALCULATIONS ARE SIGNED AND |
| SEALED. THEY ARE ONLY SIGNED AS SUBMITTED. |
| 13-103.1.1.1 |
| |
| 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS |
| AS REQUIRED PER FAC 61G1-16.004. |
| PLEASE SEE THE MISSING PRINTED NAME AND PRINTED LICENSE |
| NUMBER FOR THE ARCHITECT OF RECORD. |
| |
| 4) NOTE: PLEASE SEE 408.4 WHICH REQUIRE THE CIRCUITING |
| TO BE SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY |
| FEED. |
| PLEASE KNOW THESE CAN BE DONE BY THE ROOM NAME OR |
| NUMERICAL DESIGNATION. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE |
| CODE. |
| |
| *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| 5) NOTE: PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON |
| TITLE BLOCKS. |
| PLEASE SEE AS APPLIED IS 1720 E CENTREPARK DR. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |