Plan Review Notes
Plan Review Notes For Permit 07040753
Permit Number 07040753
Review Stop E
Sequence Number 1
Notes
Date Text
2007-04-30 15:21:42** UNSAT **
  
 ** PLEASE SEE THAT ANY REFERENCES TO THE FBC CHAPTER 1
 ARE FROM THE ADMINISTRATIVE CODE ADOPTED BY THE CITY OF
 WEST PALM BEACH.
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
  
 2) NOTE: PLEASE SEE 2004 FBC CHAPTER 13 W/ 2006
 REVISIONS.
 PLEASE SEE MISSING LIGHTING CONTROLS PER
 13-415.1.ABC.1.1, .1.2. A LIGHTING CONTACTOR IS
 INDICATED, HOWEVER NO TIMES SCHEDULING, NO TIME OVER
 RIDES, ETC ARE SHOWN.
 PLEASE SEE THE WRONG EDITION OF THE FLORIDA ENERGY CODE
 IS SHOWN AND CALCULATED.
 PLEASE CORRELATE THE LIGHTING AS SHOWN ON PLANS WITH
 THAT OF THE FIXTURES, WATTAGES ETC AS SHOWN ON
 CALCULATIONS.
 PLEASE SEE THE CONTROL FOR LIGHTING NEEDS TO COORDINATE
 WITH THE METHOD ON PLANS.
 PLEASE SEE 13-415.ABC.1.2
 PLEASE BE SURE THAT ANY OVER RIDE DEVICES ARE SHOWN ON
 PLANS AND SYMBOL LEGEND.
 PLEASE BE SURE THE ENERGY CALCULATIONS ARE SIGNED AND
 SEALED. THEY ARE ONLY SIGNED AS SUBMITTED.
 13-103.1.1.1
  
 3) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 AS REQUIRED PER FAC 61G1-16.004.
 PLEASE SEE THE MISSING PRINTED NAME AND PRINTED LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
  
 4) NOTE: PLEASE SEE 408.4 WHICH REQUIRE THE CIRCUITING
 TO BE SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY
 FEED.
 PLEASE KNOW THESE CAN BE DONE BY THE ROOM NAME OR
 NUMERICAL DESIGNATION.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN FROM THE
 CODE.
  
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON
 TITLE BLOCKS.
 PLEASE SEE AS APPLIED IS 1720 E CENTREPARK DR.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]